Parameter detail
➢
Timeout to apply action (minutes)
This parameter lets choose how much time to wait (in minutes) before executing the
action specified in the next parameter (
“Action after timeout elapsed”
).
➢
Action after timeout elapsed
When
Switch-Off
is selected, once the timeout has elapsed, the indoor unit will be
turned off.
When
Apply Preset Delta
is selected, once the timeout has elapsed, a delta
temperature will be applied in order to save energy (decreasing the setpoint when in
Heat mode, or increasing the setpoint when in Cool mode). Also new parameters will
appear.
Figure 4.37
Parameter detail
➢
Temp delta decrease (HEAT) or increase (COOL) (ºC)
This parameter lets configure the delta temperature (increase or decrease)
that will be applied when the timeout has elapsed.
Important:
When there is occupancy again after the application of a delta,
the same delta will be applied inversely. (i.e. In a room with AC in cool mode
and 25ºC setpoint temperature, a
+2ºC
delta is applied after the occupancy
timeout, setting the setpoint at 27ºC because there is no occupancy in the
room. If the setpoint is raised to 29ºC during that period, when the room is
occupied again, a
-2ºC
delta will be applied and the final setpoint
temperature will then be 27ºC).
➢
Enable secondary timeout
If set to
“no”
nothing will be applied.
If set to
“yes”
, a new timeout will be enabled and two new parameters will
appear.