IntesisBox
®
KNX
– Mitsubishi Electric A.C.
User's manual r2.3 eng
© Intesis Software S.L.U. - All rights reserved
This information is subject to change without notice
IntesisBox
®
is a registered trademark of Intesis Software SLU
URL
Email
tel
http://www.intesisbox.com
[email protected]
+34 938047134
37 / 63
Figure 4.31
Parameter detail
o
If set to
“no”
the communication objects will not be shown.
o
If set to
“yes”
the communication objects will appear. To execute a scene by using
these objects, a
“1”
value has to be sent to the
scene’s object we want to execute
(i.e.
to execute scene 4, a
“1”
has to be sent to the
Control_ Execute Scene 4
object).
4.7.4
Scene “x” preset
This parameter lets define a preset for a scene (the following description is valid for all the
scenes).
Figure 4.32
Parameter detail
o
If set to
“no”
the preset for the scene “x” will be disabled.
o
If set to
“yes”
the preset will be enabled. When a scene is executed the values
configured in the preset will be aplied.
Important:
If a scene’s preset is enabled, will not be possible to modify (store) the
scene from the KNX bus.
Figure 4.33
Parameter detail