4.2.4 Enable use of + / - object for Mode
This parameter shows/hides the
Control_ Mode +/-
communication object which lets change
the indoor unit mode by using two different datapoint types.
o
If set to
“no”
the object will not be shown.
o
If set to
“yes”
the
Control_ Mode +/-
object and a new parameter will appear.
Figure 4.7
Parameter detail
➢
DPT type for +/- Mode Object
This parameter lets choose between the datapoints
0-Up / 1-Down [DPT_1.008]
and
0-Decrease / 1-Increase [DPT_1.007]
for the
Control_ Mode +/-
object.
The sequence followed when using this object is shown below:
Important:
Read the documentation of your indoor unit to check if it has FAN
mode available.
4.2.5 Enable use of bit-type Mode objects (for control)
This parameter shows/hides the bit-type
Control_ Mode
objects.
o
If set to
“no”
the objects will not be shown.
▪
Up / Increase
▪
Down / Decrease
DRY
AUTO
HEAT
COOL
FAN