2. 

Connection 

 
Connection of the DK-RC-KNX-1i to the AC indoor unit 
 

2.1  DK-RC-KNX-1i without DAIKIN Remote Controller 

 
The DK-RC-KNX-1i can be connected directly to the P1/P2 bus of the indoor unit (no Daikin 
remote controller -RC from now on- also connected in the P1 P2 bus). If this is the case, DK-
RC-KNX-1i must be configured as master (using the ETS software), see connection diagram 
below. 
 

2.2  DK-RC-KNX-1i with DAIKIN Remote Controller 

 
If a Daikin remote controller (RC) is present and connected to the P1/P2 bus, there are two 
configuration options:  
 

 

If we want to use the RC as master, its PCB switch must be set at “M” position and the 
DK-RC-KNX-1i must be configured as slave.  

 

If we want to use the RC as slave, its PCB switch must be set at “S” position and the 
DK-RC-KNX-1i must be configured as master.  

 

Check compatible Daikin remote controllers in the link provided in section 6.  

 

 

 

Figure 2.1 

Daikin RC PCB backside, MAIN/SUB switch

 

 
 
Special mention must be made with the use of Daikin’s IR wireless remote controllers, in this 
case Daikin’s IR must be slave and the DK-RC-KNX-1i must be master, otherwise not all the 
features will be available from KNX. 
 
Disconnect mains power from the AC unit and use a 2 wire cable with a diameter of 0.75mm

2

 

to  1.25mm

for  the  connection  of  DK-RC-KNX-1i,  Daikin’s  remote  controller  and  its 

corresponding indoor unit. Screw the suitably peeled cable ends in the corresponding P1/P2 
terminals of each device, as summarized in the 

Figure 2.2

.  

 
Maximum  P1/P2  bus  length  is  500  meter.  DAIKIN  RC  and  DK-RC-KNX-1i  are  polarity 
insensitive. 
 
Connection of the DK-RC-KNX-1i to the KNX bus: 
 
Disconnect power of the KNX bus. Connect the DK-RC-KNX-1i to the KNX TP-1 (EIB) bus using 
the KNX standard connector (red/grey) of the DK-RC-KNX-1i, respect polarity.  
 
Reconnect power of the KNX bus, and mains power of the AC unit. 
 
 

Summary of Contents for DK-RC-KNX-1i

Page 1: ...IntesisBox DK RC KNX 1i v2 0 User s Manual Issue Date 25 02 2016 r1 0 eng...

Page 2: ...ument is furnished under a license agreement or nondisclosure agreement The software may be used only in accordance with the terms of those agreements No part of this publication may be reproduced sto...

Page 3: ...ice IntesisBox is a registered trademark of Intesis Software SL URL Email tel http www intesis com info intesis com 34 938047134 3 66 Gateway for integration of Daikin air conditioners into KNX TP 1 E...

Page 4: ...atus 17 4 2 7 Enable use of Text object for Mode 18 4 2 8 Enable use of Legacy_ object for Mode 18 4 3 Special Modes Configuration dialog 18 4 3 1 Enable use of POWER mode 19 4 3 2 Enable use of ECONO...

Page 5: ...bus 38 4 7 3 Enable use of bit objects for scene execution 39 4 7 4 Scene x preset 39 4 8 Switch Off Timeouts Configuration dialog 41 4 8 1 Enable use of Open Window Switch off timeout function 41 4 8...

Page 6: ...odes available Power Economy Additional Heating and Additional Cooling Timeout for Open Window and Occupancy Sleep function also available Control of the AC unit based in the ambient temperature read...

Page 7: ...e If we want to use the RC as slave its PCB switch must be set at S position and the DK RC KNX 1i must be configured as master Check compatible Daikin remote controllers in the link provided in sectio...

Page 8: ...38047134 8 66 Connections diagrams DK RC KNX 1i without DAIKIN RC DK RC KNX 1i with DAIKIN RC Figure 2 2 Connections diagrams Max 500 m P1 P2 Connection to P1 P2 bus Two wires cable KNX TP 1 EIB bus P...

Page 9: ...d setup This is a fully compatible KNX device which must be configured and setup using standard KNX tool ETS ETS database for this device can be downloaded from http www intesis com down eib DK RC KNX...

Page 10: ...first time the gateway shows the following default parameter configuration Figure 4 1 Default parameter configuration With this configuration it s possible to send On Off Control_ On Off change the A...

Page 11: ...ry to have any BRC remote controller in this case but if there are they must be configured as slaves The next parameter is also shown when selecting DK RC KNX 1i as master in P1 P2 bus Figure 4 3 Para...

Page 12: ...th the response when received Figure 4 4 Parameter detail Delay before sending READs sec With this parameter a delay can be configured between 0 and 30 seconds for the READs sent by the Control_ objec...

Page 13: ...happens Important If an initial scene is enabled and it has as Value for Remote Lock unchanged or unlocked this would unlock the remote controller because the initial scene has priority over the Contr...

Page 14: ...different from the existing one Important If the stored value is 0 hours the gateway will not send the status to KNX 4 1 7 Enable object Error Code 2byte This parameter shows hides the Status_ Error...

Page 15: ...ue and Dry mode with a 14 value 4 2 1 When mode is AUTO Status_ objs report actual operating status This parameter shows the real status of the indoor unit when Auto mode is enabled o If set to no whe...

Page 16: ...rcentage demand is meant to be applied on a fluid valve of the heating cooling system DK RC KNX 1i device does not provide individual control on the internal parts of the indoor unit as can be its com...

Page 17: ...ill appear Figure 4 8 Parameter detail DPT type for Mode Object This parameter lets choose between the datapoints 0 Up 1 Down DPT_1 008 and 0 Decrease 1 Increase DPT_1 007 for the Control_ Mode object...

Page 18: ...the object will not be shown o If set to yes the Status_ Mode Text object will appear Also in the parameters will be shown five text fields one for each mode that will let modify the text string disp...

Page 19: ...a value concerning On Off Mode Fan Speed or Setpoint Temperature is received from KNX while any Special Mode is running 1 the Special Mode will stop and the previous state will be recovered The value...

Page 20: ...Number of degrees Celsius that will increase in Heat Mode or decrease in Cool Mode while in Power Mode Fan Speed for this mode Fan Speed that will be set in the unit while in Power Mode 4 3 2 Enable...

Page 21: ...et to yes the Control_ Start Additional Heat Mode and Status_ Additional Heat Mode objects and new parameters will appear When a 1 value is sent to the Control_ communication object Additional Heating...

Page 22: ...r When a 1 value is sent to the Control_ communication object Additional Cooling Mode will be enabled and the Status_ object will return this value When a 0 value is sent to the Control_ communication...

Page 23: ...are available in the indoor unit 2 or 3 speeds available Figure 4 13 Parameter detail Changing the fan speeds will also change the fan speed byte type object and the bit type objects erasing all the g...

Page 24: ...last one sending a 3 The Status_ object will always return the value for the fan speed selected Important In both cases if a 0 value is sent to the Control_ object the minimum fan speed will be select...

Page 25: ...value between 84 and 100 is sent to the Control_ object the third speed will be selected The Status_ object will return a 33 when the first speed is selected a 67 for the second one and a 100 for the...

Page 26: ...lower limit This parameter lets choose if roll over will be enabled yes or disabled no for the Control_ Fan Speed object 4 4 4 Enable use of bit type Fan Speed objects for Control This parameter show...

Page 27: ...es the Status_ Fan Speed Text communication object o If set to no the object will not be shown o If set to yes the Status_ Fan Speed Text object will appear Also in the parameters will be shown two or...

Page 28: ...ies and communication objects 4 5 1 Indoor unit has Up Down Vanes This parameter lets you choose if the unit has Up Down Vanes available or not Figure 4 17 Parameter detail o If set to no all the para...

Page 29: ...ype for Vane Up Down With this parameter is possible to change de DPT for the Control_ Vane Up Down and Status_ Vane Up Down byte type communication objects Datapoints Scaling DPT_5 001 and Enumerated...

Page 30: ...irst vane position a 40 for the second one a 60 for the third one an 80 for the fourth one and a 100 for the fifth and last one 4 5 4 Enable use of obj for Vane Up Down This parameter shows hides the...

Page 31: ...wn object 4 5 5 Enable use of bit type Vane U D objects for Control This parameter shows hides the bit type Control_ Vane Up Down objects o If set to no the objects will not be shown o If set to yes t...

Page 32: ...the Status_ Vane Up Down Text object will appear Also in the parameters will be shown six text fields five for the Vane Position and one for the Swing function that will let modify the text string dis...

Page 33: ...nication objects 4 6 1 Periodic sending of Status_ AC Setp This parameter lets you change the interval of time in seconds from 0 to 255 at the end of which the AC setpoint temperature is sent to the K...

Page 34: ...rameter will only be available for the only cylically and cyclically and on change options and lets you change the interval of time in seconds from 1 to 255 at the end of which the AC return temperatu...

Page 35: ...oint temperature Important If a setpoint temperature above the upper defined limit or below the lower defined limit is sent through the Control_ Setpoint Temperature object it will be ALWAYS applied t...

Page 36: ...s requires programming the AC indoor unit to work as explained in option 1 above As in this case the AC return temperature could be different as of the KNX ambient temperature the DK RC KNX 1i applies...

Page 37: ...or the supervision control of multiple indoor units it will report the actual setpoint and ambient temperature on the AC indoor units which may be different than the ones at the KNX side 4 7 Scene Con...

Page 38: ...communication objects will not be shown o If set to yes the communication objects and a new parameter will appear To store a scene through the byte type object a value from 128 to 132 has to be sent t...

Page 39: ...o If set to yes the communication objects will appear To execute a scene by using these objects a 1 value has to be sent to the scene s object we want to execute i e to execute scene 4 a 1 has to be...

Page 40: ...ne x Value for Vane Up Down This parameter lets you choose the vane position of the indoor unit when the scene is executed The following options are available POSITION 1 POSITION 2 POSITION 3 POSITION...

Page 41: ...Enable use of Open Window Switch off timeout function This parameter shows hides the Control_ Switch Off Timeout communication object which lets you Start Stop a timeout to switch off the indoor unit...

Page 42: ...These commands will be used in the next parameter if set to yes Reload last On Off val once window is closed If set to no once the switch off timeout is stopped any value will be reloaded If set to y...

Page 43: ...eat mode or increasing the setpoint when in Cool mode Also new parameters will appear Figure 4 34 Parameter detail Temp delta decrease HEAT or increase COOL C This parameter lets configure the delta t...

Page 44: ...new parameters will appear Temp delta decrease HEAT or increase COOL C This parameter lets configure the delta temperature that will be applied when the timeout is extinguished Important When there i...

Page 45: ...out period no action will be performed 4 8 3 Enable use of SLEEP timeout This parameter shows hides the Control_ Start Sleep Timeout communication object which lets you start a timeout to automaticall...

Page 46: ...binary inputs properties and communication objects 4 9 1 Enable use of Input x This parameter enables the use of the Input x and shows hides the Status_ Inx communication object s which will act as co...

Page 47: ...2 1 True Disable 0 False Enable is selected the input can be disabled using the value 1 and enabled using the value 0 4 9 5 Function This parameter lets choose the function that will have the binary i...

Page 48: ...am will be sent Value on rising edge This parameter lets select the value that the Binary Input x will send on a rising edge contact activated When On is selected the binary input will always send tel...

Page 49: ...e below When Always is selected the binary input will send any value cyclically Also a new parameter will appear see below When Never is selected cyclical sending will be disabled Period for cyclical...

Page 50: ...n On increase is selected the binary input will always send telegrams with a 1 value for a short operation and an increase step for a long operation When Off decrease is selected the binary input will...

Page 51: ...or the cyclical sending of a long operation o When Shutter Blind is selected the communication objects and new parameters for the Input x will appear as shown below Figure 4 44 Parameter detail Send t...

Page 52: ...thod for the shutter blind When Step Move Step is selected On a rising edge contact activated a step stop telegram will be sent and will begin a time called T1 If a falling edge occurs contact deactiv...

Page 53: ...s parameter lets select if the Binary Input x will send a telegram or not after a bus recovery and the type of telegram sent if enabled When No action is selected no telegram will be sent after a bus...

Page 54: ...efined in the next parameter on a rising edge contact activated Figure 4 49 Parameter detail Scene when contact is activated This parameter lets choose the scene that will be activated on a rising edg...

Page 55: ...38047134 55 66 5 Specifications Dimensions 70 X 70 X 28 mm Weight 70 g KNX current consumption 5 mA P1 P2 Bus current consumption 45 mA Operating Temperature 25 85 C Stock Temperature 40 85 C Isolatio...

Page 56: ...notice IntesisBox is a registered trademark of Intesis Software SL URL Email tel http www intesis com info intesis com 34 938047134 56 66 6 AC Unit Types compatibility A list of Daikin indoor unit mo...

Page 57: ...ensor error 48 CF High pressure switch sensor 49 E0 Outdoor Unit Protection devices activated 50 E1 Outdoor uni9t PCB assembly failure 52 E3 High pressure switch HPS activated 53 E4 Low pressure switc...

Page 58: ...phase Open phase 147 U2 Power voltage failure Instantaneous power failure 148 U3 Failure to carry out check operation transmission error 149 U4 Communication error between indoor unit and outdoor uni...

Page 59: ...ature sensor error 262 35 Outdoor air temperature sensor error 263 36 Remote controller temperature sensor error 267 3A Water leakage sensor 1 error 268 3H Water leakage sensor 2 error 269 3C Dew cond...

Page 60: ...0 W T 0 Cool 1 Heat 3 Control_ Mode Cool On 1 byte DPT_Scaling 5 001 W T 0 Off 0 1 100 On Cool 4 Control_ Mode Heat On 1 byte DPT_Scaling 5 001 W T 0 Off 0 1 100 On Heat 5 Control_ Mode Auto 1 bit DPT...

Page 61: ...ne Up Down 5 pos 1 byte DPT_Scaling 5 001 W T 0 29 Pos1 30 49 Pos2 50 69 Pos3 70 89 Pos4 90 100 Pos5 Control_ Vane Up Down 5 pos 1 byte DPT_Enumerated 5 010 W T 1 Pos1 2 Pos2 3 Pos3 4 Pos4 5 Pos5 17 C...

Page 62: ...30 Control_ Lock Remote Control 1 bit DPT_Bool 1 002 W T 0 Unlocked 1 Locked 31 Control_ Lock Control Objects 1 bit DPT_Bool 1 002 W T 0 Unlocked 1 Locked Special Modes 32 Control_ Power Mode 1 bit D...

Page 63: ...ntrol_ Disable Input 2 1 bit DPT_Bool 1 002 W T 0 Enable 1 Disable Control_ Disable Input 2 1 bit DPT_Enable 1 003 W T 0 Disable 1 Enable 49 Control_ Disable Input 3 1 bit DPT_Bool 1 002 W T 0 Enable...

Page 64: ...63 Status_ Fan Speed 2 1 bit DPT_Bool 1 002 R T 1 Speed 2 64 Status_ Fan Speed 3 1 bit DPT_Bool 1 002 R T 1 Speed 3 65 Status_ Fan Speed Text 14 byte DPT_String_8859_1 16 001 R T ASCII String Vanes 66...

Page 65: ...des 81 Status_ Power Mode 1 bit DPT_Switch 1 001 R T 0 Off 1 On 82 Status_ Econo Mode 1 bit DPT_Switch 1 001 R T 0 Off 1 On 83 Status_ Additional Heat 1 bit DPT_Switch 1 001 R T 0 Off 1 On 84 Status_...

Page 66: ...demark of Intesis Software SL URL Email tel http www intesis com info intesis com 34 938047134 66 66 95 97 Status_ Inx Value 2 byte DPT_Value_2_Count 8 001 R T Status_ Inx Value 2 byte DPT_Value_Temp...