IntesisBox
®
KNX - Daikin A.C. (SKY & VRV line)
User's manual r1.0 eng
© Intesis Software S.L. - All rights reserved
This information is subject to change without notice
IntesisBox
®
is a registered trademark of Intesis Software SL
URL
Email
tel
http://www.intesis.com
[email protected]
+34 938047134
24 / 66
If this DPT is selected with 2 fan speeds:
The first fan speed will be selected if a
“1”
is sent to the
Control_
object. The second
fan speed will be selected sending a
“2”
.
The
Status_
object will always return the value for the fan speed selected.
If this DPT is selected with 3 fan speeds:
The first fan speed will be selected if a
“1”
is sent to the
Control_
object. The second
one will be selected sending a
“2”
, and the last one sending a
“3”
.
The
Status_
object will always return the value for the fan speed selected.
Important:
In both cases if a
“0”
value is sent to the Control_ object, the minimum
fan speed will be selected. If a value bigger than
“2”
(in case of 2 speeds) or bigger
than
“3”
(in case of 3 fan speeds) is sent to the Control_ object, then the maximum
fan speed will be selected.
o
When
“Scaling [DPT 5.001]”
is selected,
Control_ Fan Speed
and
Status_ Fan Speed
communication objects
for this DPT will appear. Also, depending on the number of fan
speeds selected, these objects will be different.
If this DPT is selected with 2 fan speeds:
When a value between
0%
and
74%
is sent to the
Control_
object the first fan speed will
be selected.
When a value between
75%
and
100%
is sent to the
Control_
object, the second speed
will be selected.
The
Status_
object will return a
50%
for the first fan speed, and a
100%
for the second
one.