Figure 4.11
Parameter detail
When a
“1”
value is sent to the
Control_
communication object Power Mode
will be enabled, and the
Status_
object will return this value.
When a
“0”
value is sent to the
Control_
communication object, Power Mode
will be disabled, and the
Status_
object will return this value.
Important:
This mode will ONLY work if the indoor unit is both turned on and
in a Heat, Cool, Auto-Heat or Auto-Cool Mode.
Action time for this mode (minutes):
Duration of Power Mode, in minutes, once started.
Setpoint delta increase (HEAT) or decrease (COOL) – in Celsius:
Number of degrees Celsius that will increase in Heat Mode, or decrease in Cool Mode,
while in Power Mode.
Fan Speed for this mode:
Fan Speed that will be set in the unit while in Power Mode.
4.3.2 Enable use of ECONOMY mode
This parameter shows/hides the
Control_ Start Econo Mode
and
Status_ Econo Mode
communication objects. The Econo Mode lets change the Setpoint Temperature and the Fan
Speed within a given period of time.
o
If set to
“no”
the objects will not be shown.
o
If set to
“yes”
the
Control_ Start Econo Mode
and
Status_ Econo Mode
objects and new
parameters will appear.
When a
“1”
value is sent to the
Control_
communication object, EconoMode
will be enabled, and the
Status_
object will return this value.
When a
“0”
value is sent to the
Control_
communication object, EconoMode
will be disabled, and the
Status_
object will return this value.
Important:
This mode will ONLY work if the indoor unit is both turned on and
in a Heat, Cool, Auto-Heat or Auto-Cool Mode.
Action time for this mode (minutes):
Duration of EconoMode, in minutes, once started.