This parameter lets you choose between the datapoints
0-Open / 1-Closed Window
[DPT_1.009]
and
0-Stop / 1-Start Timeout [DPT_1.010]
for the
Control_ Switch
Off Timeout
.
Disallow On/Off operation while window is Open
If set to
“no”
, On/Off commands while the window is open will be accepted.
If a
“1”
value is sent to the
Control_ Switch Off Timeout
object the switch-off
timeout period will begin again.
If a
“0”
value is sent to
the
Control_ Switch Off Timeout
object, no action will
be performed.
If set to
“yes”
, On/Off commands, while the window is open, will be saved (but not
applied). These commands will be used in the next parameter if set to
“yes”
.
Reload last On/Off val once window is closed?
If set to
“no”
, once the switch-off timeout is stopped, any value will be reloaded.
If set to
“yes”
, once the switch-off timeout is stopped, the last On/Off value sent will
be reloaded.
If a
“1”
value is sent to
the
Control_ Switch Off Timeout
object after the timeout
period, the indoor unit will
turn on
.
If a
“0”
value is sent to
the
Control_ Switch Off Timeout
after the timeout
period, no action will be performed.
4.8.2 Enable use of Occupancy function
This parameter shows/hides the
Control_ Occupancy
communication object which lets you
apply different parameters to the indoor unit depending on the presence/no presence in the
room.
o
If set to
“no”
the object will not be shown.
o
If set to
“yes”
the
Control_ Occupancy
object and new parameters will appear. If a
“1”
value is sent to this object (no room occupancy), the timeout will begin. If a
“0”
value is
sent to this object, the timeout will stop.
Figure 4.33
Parameter detail
Timeout to apply action (minutes)