This parameter lets configure a delay (in seconds) that will be applied after a
bus recovery and, after which, a telegram will be sent.
Operation
This parameter lets select the value that the Binary Input “x” will send on a rising edge
(contact activated).
When
“Up”
is selected, the binary input will always send telegrams with a
“0”
.
When
“Down”
is selected, the binary input will always send telegrams with a
“1”
value.
When
“Toggle (Up/Down)”
is selected the binary input will send a
“0”
value
after a
“1”
value and viceversa.
Method
This parameter lets select the working method for the shutter/blind.
When
“Step-Move-Step”
is selected: On a rising edge (contact activated) a
step/stop telegram will be sent and will begin a time called
T1
. If a falling edge
occurs (contact deactivated) during the
T1
, no action will be performed.
If the rising edge is maintained longer than
T1
, a move telegram will be sent
and will start a time called
T2
. If a falling edge occurs during the
T2
, a step/stop
telegram will be sent. If a falling edge occurs after
T2
no action will be
performed.
When
“Move-Step”
is selected: On a rising edge a move telegram will be sent
and will begin the
T2
time. If a falling edge occurs during the
T2
, a step/stop
telegram will be sent. If a falling edge occurs after
T2
no action will be
performed.
Important:
The
T1
time
have to be defined in the “Short/long operation limit
(x100ms)” parameter. Also the
T2
time have to be defined in the “Vanes adjustment
time (x100ms)” parameter.
Short/long operation limit (x100ms)
This parameter lets introduce the time period difference for the short and the long
operation (T1 time).