IntesisBox
®
KNX - Daikin A.C. (SKY & VRV line)
User's manual r1.0 eng
© Intesis Software S.L. - All rights reserved
This information is subject to change without notice
IntesisBox
®
is a registered trademark of Intesis Software SL
URL
Email
tel
http://www.intesis.com
[email protected]
+34 938047134
50 / 66
When
“Off”
is selected, the binary input will send a telegram with a
“0”
value
after a bus recovery. Also a new parameter will appear (see below).
Figure 4.43
Parameter detail
Sending delay after a bus recovery (seconds)
This parameter lets configure a delay (in seconds) that will be applied after a
bus recovery and, after which, a telegram will be sent.
Mode for short (long) operation
This parameter lets select the value that the Binary Input “x” will send on a rising edge
(contact activated), for a short and a long operation.
When
“On (increase)”
is selected, the binary input will always send telegrams
with a
“1”
value for a short operation, and an
“increase step”
for a long
operation.
When
“Off (decrease)”
is selected, the binary input will always send
telegrams with a
“0”
value for a short operation, and an
“decrease step”
for
a long operation.
When
“Toggle: On/Off (increase/decrease)”
is selected:
o
For the short operation the binary input will send a
“1”
value after a
“0”
value and viceversa.
o
For the long operation the binary input will send an
“increase step”
after
a
“decrease step”
and viceversa.
Important:
Note that the first long operation in toggle depends on the last short
operation, meaning that after a
“1”
value will be sent a
“decrease step”
and after a
“0”
value will be sent an
“increase step”
.
Important:
The time period between a short and a long operation is defined in the
parameter “Short/long operation limit (x100ms)”.
Increasing step
This parameter lets select the increasing step value (in %) that will be sent for a long
operation.
Decreasing step