75
Status_ AC Return Temp
2 byte
DPT_Value_Temp
9.001
R
T ºC value in EIS5 format
Error
76
Status_ Error/Alarm
1 bit
DTP_Alarm
1.005
R
T 0 - No Alarm; 1 - Alarm
77
Status_ Error Code
2 byte
Enumerated
R
T 0 - No Error; Any other see user's manual
78
Status_ Error Text code
14 byte DPT_String_8859_1 16.001
R
T 2 char Daikin Error; Empty - none
Locking
79
Status_Lock Remote Control
1 bit
DPT_Bool
1.002
W T 0 - Unlocked; 1 - Locked
80
Statu_Lock Control Objects
1 bit
DPT_Bool
1.002
W T 0 - Unlocked; 1 - Locked
Special
Modes
81
Status_ Power Mode
1 bit
DPT_Switch
1.001
R
T 0 - Off; 1-On
82
Status_ Econo Mode
1 bit
DPT_Switch
1.001
R
T 0 - Off; 1-On
83
Status_ Additional Heat
1 bit
DPT_Switch
1.001
R
T 0 - Off; 1-On
84
Status_ Additional Cool
1 bit
DPT_Switch
1.001
R
T 0 - Off; 1-On
Counter
85
Status_ Operation Hour Counter
2 byte
DPT_Value_2_Ucou
nt
7.001
R
T Number of operating hours
Scene
86
Status_ Current Scene
1 byte
DPT_SceneNumber
17.001
R
T 0 to 4 - Scene 1 to 5; 63 - No Scene
Legacy
87
Legacy_ Mode
1 byte
Enumerated
R
T 0 - Auto; 1 - Heat; 2 - Dry; 3 - Fan; 4 - Cool
88
Legacy_ Fan Speed
1 byte
Enumerated
R
T 0 - Speed 1; 1 - Speed 2; 2 - Speed 3
89
Legacy_ Vane Up-Down
1 byte
Enumerated
R
T 0 to 4 - Pos 1 to Pos 5; 5 - Swing
Binary
Inputs
90
92
94
96
Status_ Inx - Switching
1 bit
DPT_Switch
1.001 R T
Status_ Inx – Dimming - On/Off
1 bit
DPT_Switch
1.001 R T
Status_ Inx – Shut/Blind - Step
1 bit
DPT_ShutterBlinds
1.023 R T
91
93
Status_ Inx – Value
1 byte
DPT_Value_1_Ucount
5.010 R T
Status_ Inx – Value
2 byte
DPT_Value_2_Ucount
7.001 R T