7 Battery Capacity Test or Discharge Operation
7.1
Capacity Test To Time
This mode will discharge the battery at the predefined current until the set time has
elapsed. If the battery target voltage has not been reached the unit will stop and report
a capacity test of 100%. This reported capacity is the minimum capacity of the battery.
If the battery target voltage is reached before the set time the unit will stop and report
the capacity calculated as follows: -
The parameters required for this mode are as follows: -
Target Volts :
This is the point at which the discharge will stop.
Discharge Amps :
This is the constant current amps to discharge the battery. This is
usually the A/H rating of the battery.
Test Time :
This is the maximum time at which the discharge test is to be performed.
This is usually 1 Hour.
Doc: DWG1042-12-R18 MB73P+ Operators manual.odt
Page 32 of 64
Copyright Material of Intelligent Charging Limited © 2020
Printed On : 29/11/20
ACTUAL CAPTEST TIME
CAPTEST TIME
100
X
%BATTERY CAPACITY =
MAINTAIN
TEST
CURRENT
STOP CAPTEST
TARGET
VOLTAGE
REACHED
?
START
HAS TIME
ELAPSED
?
CLR KEY
PRESSED
?
NO
YES
NO
YES
NO
YES