Description of Function Codes
MD380 User Manual
- 210 -
F
unction Code
Parameter Name
Setting Range
Default
F
A-12
PID feedback
fi
lter time
0.00–60.00s
0.00s
F
A-13
PID output
fi
lter time
0.00–60.00s
0.00s
FA-12 is used to filter the PID feedback, helping to reduce interference on the feedback but
slowing the response of the process closed-loop system.
FA-13 is used to filter the PID output frequency, helping to weaken sudden change of the AC
drive output frequency but slowing the response of the process closed-loop system.
F
unction Code
Parameter Name
Setting Range
Default
F
A-15
Proportional gain Kp2
0.0–100.0
20.0
F
A-16
Integral time Ti2
0.01–10.00s
2.00s
F
A-17
Differential time Td2
0.000–10.000s
0.000s
F
A-18
PID parameter switchover
condition
0: No switchover
1: Switchover via DI
2: Automatic switchover
based on deviation
0
F
A-19
PID parameter switchover
deviation 1
0.0% to
F
A-20
20.0%
F
A-20
PID parameter switchover
deviation 2
F
A-19 to 100.0%
80.0%
In some applications, PID parameters switchover is required when one group of PID
parameters cannot satisfy the requirement of the whole running process.
These parameters are used for switchover between two groups of PID parameters.
Regulator parameters FA-15 to FA-17 are set in the same way as FA-05 to FA-07.
The switchover can be implemented either via a DI terminal or automatically implemented
based on the deviation.
If you select switchover via a DI terminal, the DI must be allocated with function 43 "PID
parameter switchover". If the DI is OFF, group 1 (FA-05 to FA-07) is selected. If the DI is
ON, group 2 (FA-15 to FA-17) is selected.
If you select automatic switchover, when the absolute value of the deviation between PID
feedback and PID setting is smaller than the value of FA-19, group 1 is selected. When the
absolute value of the deviation between PID feedback and PID setting is higher than the
value of FA-20, group 2 is selected. When the deviation is between FA-19 and FA-20, the
PID parameters are the linear interpolated value of the two groups of parameter values.
Summary of Contents for HD380-5T0.7GB
Page 1: ...High Performance AC Drive MD380...
Page 9: ......
Page 10: ...1 Safety Information and Precautions...
Page 17: ...Safety Information and Precautions MD380 User Manual 16...
Page 18: ...2 Product Information...
Page 29: ...Product Information MD380 User Manual 28...
Page 30: ...3 Mechanical and Electrical Installation...
Page 46: ...4 Operation Display and Application Examples...
Page 79: ...Operation Display and Application Examples MD380 User Manual 78...
Page 80: ...5 Function Code Table...
Page 136: ...6 Description of Function Codes...
Page 248: ...7 EMC...
Page 260: ...8 Selection and Dimensions...
Page 285: ...Selection and Dimensions MD380 User Manual 284...
Page 286: ...9 Maintenance and Troubleshooting...