MD380 User Manual Desc
ription of Function Codes
- 197 -
F
unction Code
Parameter Name
Setting Range
Default
F
8-48
Cooling fan control
0:
F
an working during running
1:
F
an working continuously
0
It is used to set the working mode of the cooling fan. If this parameter is set to 0, the fan
works when the AC drive is in running state. When the AC drive stops, the cooling fan
works if the heatsink temperature is higher than 40°C, and stops working if the heatsink
temperature is lower than 40°C.
If this parameter is set to 1, the cooling fan keeps working after power-on.
F
unction Code
Parameter Name
Setting Range
Default
F
8-49
Wakeup frequency
Dormant frequency (
F
8-51) to
maximum frequency (
F
0-10)
0.00 Hz
F
8-50
Wakeup delay time
0.0–6500.0s
0.0s
F
8-51
Dormant frequency
0.00 Hz to wakeup frequency (
F
8-49)
0.00 Hz
F
8-52
Dormant delay time
0.0–6500.0s
0.0s
These parameters are used to implement the dormant and wakeup functions in the water
supply application.
When the AC drive is in running state, the AC drive enters the dormant state and stops
automatically after the dormant delay time (F8-52) if the set frequency is lower than or equal
to the dormant frequency (F8-51).
When the AC drive is in dormant state and the current running command is effective, the AC
drives starts up after the wakeup delay time (F8-50) if the set frequency is higher than or
equal to the wakeup frequency (F8-49).
Generally, set the wakeup frequency equal to or higher than the dormant frequency. If the
wakeup frequency and dormant frequency are set to 0, the dormant and wakeup functions
are disabled.
When the dormant function is enabled, if the frequency source is PID, whether PID
operation is performed in the dormant state is determined by FA-28. In this case, select PID
operation enabled in the stop state (FA-28 = 1).
F
unction Code
Parameter Name
Setting Range
Default
F
8-53
Current running time reached
0.0–6500.0 min
0.0 min
If the current running time reaches the value set in this parameter, the corresponding DO
becomes ON, indicating that the current running time is reached.
F
unction Code
Parameter Name
Setting Range
Default
F
8-54
Output power correction coef
fi
cient
0.00%–200 .0%
100.0%
When the output power (U0-05) is not equal to the required value, you can perform linear
correction on output power by using this parameter.
Summary of Contents for HD380-5T0.7GB
Page 1: ...High Performance AC Drive MD380...
Page 9: ......
Page 10: ...1 Safety Information and Precautions...
Page 17: ...Safety Information and Precautions MD380 User Manual 16...
Page 18: ...2 Product Information...
Page 29: ...Product Information MD380 User Manual 28...
Page 30: ...3 Mechanical and Electrical Installation...
Page 46: ...4 Operation Display and Application Examples...
Page 79: ...Operation Display and Application Examples MD380 User Manual 78...
Page 80: ...5 Function Code Table...
Page 136: ...6 Description of Function Codes...
Page 248: ...7 EMC...
Page 260: ...8 Selection and Dimensions...
Page 285: ...Selection and Dimensions MD380 User Manual 284...
Page 286: ...9 Maintenance and Troubleshooting...