MD380 User Manual Desc
ription of Function Codes
- 237 -
F
unction Code
Parameter Name
Setting Range
Default
A8-02
Slave following
master command
selection
0: Slave not following running
commands of the master
1: Slave following running commands
of the master
0
When A8-01 (Master and slave selection) is set to 1 (Slave) and F0-02 (Command source
selection) is set to 2 (Communication control), if A8-02 is set to 1, the salve follows the
master to start or stop.
F
unction Code
Name
Setting Range
Default
A8-03
Usage of data received by slave
0: Torque setting
1:
F
requency setting
0
It is used to determine whether the slave uses data received from the master for torque
setting or frequency setting. This function can be used only when the frequency source or
torque source must be communication setting.
When the AC drive is a slave in point-point communication and receives data for torque
setting, 100.00% of the received data corresponds to 200.0% of torque setting, unrelated
to A0-03. If zero offset of the slave is 0.00% and the gain is 1.00, it means that the slave
directly takes the output torque of the master as the target torque.
When the AC drive is a slave in point-point communication and receives data for frequency
setting, 100.00% of the received data corresponds to the value of F0-10 (Maximum frequency).
For example, to balance the load, do the following settings.
Table 6-14 Settings for balancing the load
Master
Slave
A0-00 = 0: Speed control
A0-00 = 1: Torque control
A8-00 = 1: Point-point communication
enabled
A8-00 = 1: Point-point communication enabled
A8-01 = 0: Master in point-point
communication
A8-01 = 1: Slave in point-point communication
A8-02 = 0: Data source from master being
output torque
A8-03 = 0: Slave receiving data for torque setting
A0-01 = 5: Torque source in torque control set to
communication setting
F
unction Code
Parameter Name
Setting Range
Default
A8-04
Z
ero offset of received data (torque)
-100.00%–100.00%
0.00%
A8-05
Gain of received data (torque)
-10.00–10.00
1.00
These two parameters are used to adjust data received from the master and define the
torque reference relationship between the master and the slave.
Summary of Contents for HD380-5T0.7GB
Page 1: ...High Performance AC Drive MD380...
Page 9: ......
Page 10: ...1 Safety Information and Precautions...
Page 17: ...Safety Information and Precautions MD380 User Manual 16...
Page 18: ...2 Product Information...
Page 29: ...Product Information MD380 User Manual 28...
Page 30: ...3 Mechanical and Electrical Installation...
Page 46: ...4 Operation Display and Application Examples...
Page 79: ...Operation Display and Application Examples MD380 User Manual 78...
Page 80: ...5 Function Code Table...
Page 136: ...6 Description of Function Codes...
Page 248: ...7 EMC...
Page 260: ...8 Selection and Dimensions...
Page 285: ...Selection and Dimensions MD380 User Manual 284...
Page 286: ...9 Maintenance and Troubleshooting...