Maintenance and
Troubleshooting
MD380 User Manual
- 290 -
F
ault Name
Display
Possible Causes
Solutions
Motor overload
Err11
1:
F
9-01 is set improperly.
2: The load is too heavy or locked-
rotor occurs on the motor.
3: The AC drive model is of too
small power class.
1: Set
F
9-01 correctly.
2: Reduce the load and
check the motor and the
mechanical condition.
3: Select an AC drive of
higher power class.
Power input
phase loss
Err12
1: The three-phase power input is
abnormal.
2: The drive board is faulty.
3: The lightening board is faulty.
4: The main control board is faulty.
1: Eliminate external faults.
2: Contact the agent or
Inovance.
Power output
phase loss
Err13
1: The cable connecting the AC
drive and the motor is faulty.
2: The AC drive's three-phase
outputs are unbalanced when the
motor is running.
3: The drive board is faulty.
4: The module is faulty.
1: Eliminate external faults.
2: Check whether the motor
three-phase winding is
normal.
3: Contact the agent or
Inovance.
Module overheat
Err14
1: The ambient temperature is too
high.
2: The air
fi
lter is blocked.
3: The fan is damaged.
4: The thermally sensitive resistor
of the module is damaged.
5: The inverter module is
damaged.
1: Lower the ambient
temperature.
2: Clean the air
fi
lter.
3: Replace the damaged fan.
4: Replace the damaged
thermally sensitive resistor.
5: Replace the inverter
module.
External
equipment fault
Err15
1: External fault signal is input via
DI.
2: External fault signal is input via
virtual I/O.
Reset the operation.
Communication
fault
Err16
1: The host computer is in
abnormal state.
2: The communication cable is
faulty.
3:
F
0-28 is set improperly.
4: The communication parameters
in group
F
D are set improperly.
1: Check the cabling of host
computer.
2: Check the communication
cabling.
3: Set
F
0-28 correctly.
4: Set the communication
parameters properly.
Contactor fault
Err17
1: The drive board and power
supply are faulty.
2: The contactor is faulty.
1: Replace the faulty drive
board or power supply board.
2: Replace the faulty
contactor.
Summary of Contents for HD380-5T0.7GB
Page 1: ...High Performance AC Drive MD380...
Page 9: ......
Page 10: ...1 Safety Information and Precautions...
Page 17: ...Safety Information and Precautions MD380 User Manual 16...
Page 18: ...2 Product Information...
Page 29: ...Product Information MD380 User Manual 28...
Page 30: ...3 Mechanical and Electrical Installation...
Page 46: ...4 Operation Display and Application Examples...
Page 79: ...Operation Display and Application Examples MD380 User Manual 78...
Page 80: ...5 Function Code Table...
Page 136: ...6 Description of Function Codes...
Page 248: ...7 EMC...
Page 260: ...8 Selection and Dimensions...
Page 285: ...Selection and Dimensions MD380 User Manual 284...
Page 286: ...9 Maintenance and Troubleshooting...