MD380 User Manual Desc
ription of Function Codes
- 155 -
F
unction Code
Parameter Name
Setting Range
Default
F
2-13
Excitation adjustment proportional gain
0–20000
2000
F
2-14
Excitation adjustment integral gain
0–20000
1300
F
2-15
Torque adjustment proportional gain
0–20000
2000
F
2-16
Torque adjustment integral gain
0–20000
1300
These are current loop PI parameters for vector control. These parameters are automatically
obtained through "Asynchronous motor complete auto-tuning" or "Synchronous motor no-
load auto-tuning", and need not be modified.
The dimension of the current loop integral regulator is integral gain rather than integral time.
Note that too large current loop PI gain may lead to oscillation of the entire control loop.
Therefore, when current oscillation or torque fluctuation is great, manually decrease the
proportional gain or integral gain here.
F
unction Code
Parameter Name
Setting Range
Default
F
2-18
F
ield weakening mode of
synchronous motor
0: No
fi
eld weakening
1: Direct calculation
2: Automatic adjustment
1
F
2-19
F
ield weakening depth of
synchronous motor
50%–500%
100%
F
2-20
Maximum
fi
eld weakening current
1%–300%
50%
F
2-21
F
ield weakening automatic
adjustment gain
10%–500%
100%
F
2-22
F
ield weakening integral multiple
2–10
2
These parameters are used to set field weakening control for the synchronous motor.
If F2-18 is set to 0, field weakening control on the synchronous motor is disabled. In this
case, the maximum rotational speed is related to the AC drive bus voltage. If the motor's
maximum rotational speed cannot meet the requirements, enable the field weakening
function to increase the speed.
The MD380 provides two field weakening modes: direct calculation and automatic
adjustment.
•
In direct calculation mode, directly calculate the demagnetized current and manually
adjust the demagnetized current by means of F2-19. The smaller the demagnetized
current is, the smaller the total output current is. However, the desired field weakening
effect may not be achieved.
•
In automatic adjustment mode, the best demagnetized current is selected automatically.
This may influence the system dynamic performance or cause instability.
The adjustment speed of the field weakening current can be changed by modifying the
values of F2-21 and F2-22.
A very quick adjustment may cause instability. Therefore,
generally do not modify them manually.
Summary of Contents for HD380-5T0.7GB
Page 1: ...High Performance AC Drive MD380...
Page 9: ......
Page 10: ...1 Safety Information and Precautions...
Page 17: ...Safety Information and Precautions MD380 User Manual 16...
Page 18: ...2 Product Information...
Page 29: ...Product Information MD380 User Manual 28...
Page 30: ...3 Mechanical and Electrical Installation...
Page 46: ...4 Operation Display and Application Examples...
Page 79: ...Operation Display and Application Examples MD380 User Manual 78...
Page 80: ...5 Function Code Table...
Page 136: ...6 Description of Function Codes...
Page 248: ...7 EMC...
Page 260: ...8 Selection and Dimensions...
Page 285: ...Selection and Dimensions MD380 User Manual 284...
Page 286: ...9 Maintenance and Troubleshooting...