Description of Function Codes
MD380 User Manual
- 196 -
Figure 6-24 Any current reaching detection
OFF
OFF
OFF
ON
ON
ON
Output
current
Any current
reaching
Any current reaching
detection signal
DO or relay
Any current reaching amplitude
Any current reaching amplitude
F
unction Code
Parameter Name
Setting Range
Default
F
8-42
Timing function
0: Disabled
1: Enabled
0
F
8-43
Timing duration source
0:
F
8-44
1: AI1
2: AI2
3: AI3
(100% of analog input corresponds
to the value of
F
8-44)
0
F
8-44
Timing duration
0.0–6500.0 min
0.0 min
These parameters are used to implement the AC drive timing function.
If F8-42 is set to 1, the AC drive starts to time at startup. When the set timing duration is
reached, the AC drive stops automatically and meanwhile the corresponding DO becomes
ON.
The AC drive starts timing from 0 each time it starts up and the remaining timing duration
can be queried by U0-20.
The timing duration is set in F8-43 and F8-44, in unit of minute.
F
unction Code
Parameter Name
Setting Range
Default
F
8-45
AI1 input voltage lower limit
0.00 V to
F
8-46
3.10 V
F
8-46
AI1 input voltage upper limit
F
8-45 to 10.00 V
6.80 V
These two parameters are used to set the limits of the input voltage to provide protection on
the AC drive. When the AI1 input is larger than the value of F8-46 or smaller than the value
of F8-45, the corresponding DO becomes ON, indicating that AI1 input exceeds the limit.
F
unction Code
Parameter Name
Setting Range
Default
F
8-47
Module temperature threshold
0–75 °C
75 °C
When the heatsink temperature of the AC drive reaches the value of this parameter, the
corresponding DO becomes ON, indicating that the module temperature reaches the
threshold.
Summary of Contents for HD380-5T0.7GB
Page 1: ...High Performance AC Drive MD380...
Page 9: ......
Page 10: ...1 Safety Information and Precautions...
Page 17: ...Safety Information and Precautions MD380 User Manual 16...
Page 18: ...2 Product Information...
Page 29: ...Product Information MD380 User Manual 28...
Page 30: ...3 Mechanical and Electrical Installation...
Page 46: ...4 Operation Display and Application Examples...
Page 79: ...Operation Display and Application Examples MD380 User Manual 78...
Page 80: ...5 Function Code Table...
Page 136: ...6 Description of Function Codes...
Page 248: ...7 EMC...
Page 260: ...8 Selection and Dimensions...
Page 285: ...Selection and Dimensions MD380 User Manual 284...
Page 286: ...9 Maintenance and Troubleshooting...