Description of Function Codes
MD380 User Manual
- 156 -
Group
F
3: V/
F
Control Parameters
Group F3 is valid only for V/F control.
The V/F control mode is applicable to low load applications (fan or pump) or applications
where one AC drive operates multiple motors or there is a large difference between the AC
drive power and the motor power.
F
unction Code
Parameter Name
Setting Range
Default
F
3-00
V/
F
curve setting
0: Linear V/
F
1: Multi-point V/
F
2: Square V/
F
3: 1.2-power V/
F
4: 1.4-power V/
F
6: 1.6-power V/
F
8: 1.8-power V/
F
9: Reserved
10: V/
F
complete separation
11: V/
F
half separation
0
•
0: Linear V/F
It is applicable to common constant torque load.
•
1: Multi-point V/F
It is applicable to special load such as dehydrator and centrifuge. Any such V/F curve
can be obtained by setting parameters of F3-03 to F3-08.
•
2: Square V/F
It is applicable to centrifugal loads such as fan and pump.
•
3 to 8: V/F curve between linear V/F and square V/F
•
10: V/F complete separation
In this mode, the output frequency and output voltage of the AC drive are independent.
The output frequency is determined by the frequency source, and the output voltage is
determined by "Voltage source for V/F separation" (F3-13).
It is applicable to induction heating, inverse power supply and torque motor control.
•
11: V/F half separation
In this mode, V and F are proportional and the proportional relationship can be set in
F3-13. The relationship between V and F are also related to the rated motor voltage
and rated motor frequency in Group F1.
Assume that the voltage source input is X (0 to 100%), the relationship between V and
F is:
V/F = 2 x X x (Rated motor voltage)/(Rated motor frequency)
Summary of Contents for HD380-5T0.7GB
Page 1: ...High Performance AC Drive MD380...
Page 9: ......
Page 10: ...1 Safety Information and Precautions...
Page 17: ...Safety Information and Precautions MD380 User Manual 16...
Page 18: ...2 Product Information...
Page 29: ...Product Information MD380 User Manual 28...
Page 30: ...3 Mechanical and Electrical Installation...
Page 46: ...4 Operation Display and Application Examples...
Page 79: ...Operation Display and Application Examples MD380 User Manual 78...
Page 80: ...5 Function Code Table...
Page 136: ...6 Description of Function Codes...
Page 248: ...7 EMC...
Page 260: ...8 Selection and Dimensions...
Page 285: ...Selection and Dimensions MD380 User Manual 284...
Page 286: ...9 Maintenance and Troubleshooting...