8.0 GENERAL INFORMATION
TS1A–13A
http://air.irco.com
26
TS–13A 60Hz
KEY
A.
Electrical conduit connection
B.
Compressed air inlet 6” ANSI Flange
C.
Compressed air discharge 6” ANSI Flange
D.
Condensate drain 1/4” NPT female
NOTES:
1.
Weight (approximate):
TS–13A: 786 kg (1729 lb)
2.
Refrigerant: R–404A
3.
Tolerance on dimensions:
13mm (0.5”) unless otherwise
stated.
4.
305mm (12”) minimum electrical cable length allowance is
required between the electrical cable entry (A) and the mains
terminal block.
5.
Recommended clearance on all sides 1m(3ft) front panel with
starter door may require more as defined by local and national
electrical codes.
6.
External piping shall not exert any unresolved moments or
forces on it.
7.
There should be no plastic piping, not approved by IR, attached
to this unit or used for any lines downstream.
8.
Field installed ducting to and from the dryer can not add more
than 1.0mm (0.04) water air resistance.