8.0 GENERAL INFORMATION
TS1A–13A
http://air.irco.com
14
8.1 TECHNICAL INFORMATION
COMMON TECHNICAL DATA
General
Maximum ambient temperature
_
C (
_
F)
46 (115)
Minimum ambient temperature
_
C (
_
F)
2 (35)
Refrigerant type
R404A
Refrigerant oil
ISO 32 Polyolester (POE)
Maximum standard compressed air inlet pressure, barg (psig)
(4)
1
2
.
1
(
175
)
Control settings
Hot gas valve setting, barg (psig)
(5)
5.03 – 5.66 (73 – 82)
Thermal expansion valve superheat,
_
C (
_
F)
(6)
3.3 – 5.0 (6.0 – 9.0)
High refrigerant temperature switch setting
_
C
115 (240)
High pressure switch setting barg (psig)
29.3 (425)
Fan pressure switch setting on/off barg (psig)
16.5 / 13.1 (240 / 190)
Fan temp switch setting on/off
_
C (
_
F)
99 / 82 (210 / 180)
Low pressure switch setting barg (psig)
2.8 (40)
Performance
(1)(2)
Dew point temperature at rated conditions and flow,
_
C (
_
F)
(2)
3.8 (39)
Dew point temperature at rated conditions and flow,
_
C (
_
F)
(1)
3.0 (37.4)
Air Cooling System
Maximum
∆
P across duct work, mm H
2
O (in. H
2
O)
1.0 (0.04)
(1)
All standard 230v/1/50Hz, 230v/1/60Hz, 400v/3/50Hz and 380v/3/60Hz machines: 25
_
C ambient, 7 barg inlet, 35
_
C inlet, 35
_
C dew point
inlet.
(2)
All standard 230v/3/60Hz, 460v/3/60Hz and 575v/3/60Hz machines: 85
_
F ambient, 125 psig inlet, 100
_
F inlet, 100
_
F dew point inlet.
(3)
Always apply local electrical codes for sizing cables and fusing. In absence of local codes, the minimum cable size should always be calculated
on basis of maximum package full load x1.25.
(4)
High pressure options allow machines to operate at high pressure ratings. See machine specification data decal for pressure ratings for these
machines.
(5)
The low side refrigerant pressure is factory set at 5.38 – 5.66 barg (78 – 82 psig). It may need to be adjusted at the hot gas valve periodically due
to local ambient and seasonal changes to avoid dryer freeze–up. See section 11.4 “Routine Maintenance” for the adjustment procedure.
(6)
Evaporator superheat is factory set and should not require adjustment unless it is measured out of specification when the dryer is operating at
its nominal load, and the discharge air pressure dewpoint is high.
See “Routine Maintenance” for the adjustment procedure.
Summary of Contents for TS10A
Page 2: ......
Page 10: ...5 0 SAFETY TS1A 13A http air irco com 8 5 3 TEXT DECALS NORTH AMERICA ...
Page 50: ......
Page 52: ......
Page 60: ...5 0 SECURITE TS1A 13A http air irco com 8 5 3 DÉCALCOMANIES DES TEXTES AMÉRIQUE DU NORD ...
Page 101: ......
Page 102: ......
Page 104: ......
Page 112: ...5 0 SEGURANÇA TS1A 13A http air irco com 8 5 3 AUTOCOLANTES DE TEXTO AMÉRICA DO NORTE ...
Page 152: ......
Page 161: ...5 0 SEGURIDAD TS1A 13A http air irco com 8 5 3 CALCOMANÍAS DE TEXTO AMÉRICA DEL NORTE ...
Page 203: ......
Page 204: ......