90
RT-SVD03L-EN
Table 56.
Test mode states for Voyager
™
™
Commercial CV units with modulating dehumidification and staged heat
Test
Step
Mode
Fan
Econ.
Comp 1 Comp 2 Comp 3 Heat 1
Heat 2
Pumpout
Cool
Valve
Reheat
Valve
VAV
Box
1
FAN ON
ON
MIN
OFF
OFF
OFF
OFF
OFF
OFF
100%
0%
ON
2
ECONO-
MIZER
ON
OPEN
OFF
OFF
OFF
OFF
OFF
OFF
100%
0%
ON
3
COOL 1
ON
MIN
ON
OFF
OFF
OFF
OFF
IN-
CONTROL
100%
0%
ON
4
COOL 2
ON
MIN
ON
ON
OFF
OFF
OFF
IN-
CONTROL
100%
0%
ON
5
COOL 3
ON
MIN
ON
ON
ON
OFF
OFF
IN-
CONTROL
100%
0%
ON
6
REHEAT
ON
MIN
ON
ON
ON
OFF
OFF
IN-
CONTROL
50%
50%
ON
7
HEAT 1
ON
MIN
OFF
OFF
OFF
ON
OFF
OFF
100%
0%
ON
8
HEAT 2
ON
MIN
OFF
OFF
OFF
ON
ON
OFF
100%
0%
ON
9
RESET
Notes:
1
.
2 & 3 stage standard efficiency units: For 27.5 to 35 ton units, both compressors will be energized during the Cool 2 Step. For 40-50T units,
only Compressor 2 will be energized during the Cool 2 Step.
2
.
2 & 3 stage standard efficiency units: The reheat pumpout relay will be energized any time the reheat circuit is energized in active Cooling
Mode.
3
.
2 & 3 stage standard efficiency units: For units with Statitrac™ installed, the exhaust damper will track the Economizer position during
Service Test Mode and the Exhaust Fan will be energized once the economizer rises above the exhaust enable setpoint.
4
.
2 & 3 stage standard efficiency units: Heating will not be energized during Service Test until the 6 minute VAV box ON timer has expired.
5
.
5 stage high efficiency units: Compressor 1 is the smaller compressor on the circuit.
6
.
5 stage high efficiency units: Condenser fans are controlled as defined for normal operation.
7
.
5 stage high efficiency units: Exhaust fan operates as defined for normal operation based on economizer position.
8
.
5 stage high efficiency units: When compressor 1 is energized with either C1, C2, or with both for 30 minutes continuously, C3 will be
required to de-energize for 30 seconds.
Table 57.
Test mode states for Voyager
™
™
Commercial SZ VAV units with modulating dehumidification and staged
heat
Test
Step
Mode
Fan
VFD
Command
Econ.
Comp 1 Comp 2 Comp 3 Heat 1
Heat 2
Pumpout
Cool
Valve
Reheat
Valve
1
FAN ON
ON
45% (0
VDC)
MIN
OFF
OFF
OFF
OFF
OFF
OFF
100%
0%
2
ECONO-
MIZER
ON
45% (0
VDC)
OPEN
OFF
OFF
OFF
OFF
OFF
OFF
100%
0%
3
COOL 1
ON
80% (6.67
VDC)
MIN
ON
OFF
OFF
OFF
OFF
IN-
CONTROL
100%
0%
4
COOL 2
ON
IN-
CONTROL
MIN
ON
ON
OFF
OFF
OFF
IN-
CONTROL
100%
0%
5
COOL 3
ON
IN-
CONTROL
MIN
ON
ON
ON
OFF
OFF
IN-
CONTROL
100%
0%
6
REHEAT
ON
73% (5.24
VDC)
MIN
ON
ON
ON
OFF
OFF
IN-
CONTROL
50%
50%
7
HEAT 1
ON
100% (10
VDC)
MIN
OFF
OFF
OFF
ON
OFF
OFF
100%
0%
8
HEAT 2
ON
100% (10
VDC)
MIN
OFF
OFF
OFF
ON
ON
OFF
100%
0%
9
RESET
Notes:
1
.
2 & 3 stage standard efficiency units: For Traditional VAV units, the VFD Command when “In-Control” will be controlled based on supply air
pressure requirements. For SZVAV units, the VFD command will be at discrete points during Test Mode.
2
.
2 & 3 stage standard efficiency units: For 27.5 to 35 ton units, both compressors will be energized during the Cool 2 Step. For 40-50T units,
only Compressor 2 will be energized during the Cool 2 Step.
3
.
2 & 3 stage standard efficiency units: The reheat pumpout relay will be energized any time the reheat circuit is energized in active Cooling
Mode.
4
.
2 & 3 stage standard efficiency units: For units with Statitrac™ installed, the exhaust damper will track the Economizer position during
Service Test Mode and the Exhaust Fan will be energized once the economizer rises above the exhaust enable setpoint.
5
.
5 stage high efficiency units: Compressor 1 is the smaller compressor on the circuit.
6
.
5 stage high efficiency units: Condenser fans are controlled as defined for normal operation.
7
.
5 stage high efficiency units: Exhaust fan operates as defined for normal operation based on economizer position.
8
.
5 stage high efficiency units: When compressor 1 is energized with either C1, C2, or with both for 30 minutes continuously, C3 will be required
to de-energize for 30 seconds.