58
RT-SVD03L-EN
Table 15.
Design minimum OA flow setpoints
(continued)
Design Min OA Flow
Setpoint (R130)
DCV Min OA Flow
Setpoint (R41)
Voltage
Reading
Airflow CFM
Airflow CFM
Voltage Vdc
17100
17100
2.3
17200
17200
2.31
17300
17300
2.32
17400
17400
2.33
17500
17500
2.34
17600
17600
2.35
17700
17700
2.36
17800
17800
2.37
17900
17900
2.38
18000
18000
2.39
18100
18100
2.4
18200
18200
2.41
18300
18300
2.42
18400
18400
2.43
18500
18500
2.44
18600
18600
2.45
18700
18700
2.46
18800
18800
2.47
18900
18900
2.48
19000
19000
2.49
Table 16.
OA flow adjustment setpoints
OA Flow Adjustment
(R136)
Voltage Reading
Multiplier/ Adjustment
Vdc
0.8
0
0.81
0.05
0.82
0.14
0.83
0.22
0.84
0.3
0.85
0.35
0.86
0.43
0.87
0.51
0.88
0.57
0.89
0.64
0.9
0.72
0.91
0.78
0.92
0.88
0.93
0.94
Table 16.
OA flow adjustment setpoints (continued)
OA Flow Adjustment
(R136)
Voltage Reading
Multiplier/ Adjustment
Vdc
0.94
1
0.95
1.06
0.96
1.1
0.97
1.18
0.98
1.22
0.99
1.25
1
1.3 - 1.84
1.01
1.86
1.02
1.89
1.03
1.92
1.04
1.96
1.05
2
1.06
2.03
1.07
2.06
1.08
2.1
1.09
2.12
1.1
2.14
1.11
2.16
1.12
2.18
1.13
2.2
1.14
2.24
1.15
2.26
1.16
2.28
1.17
2.3
1.18
2.34
1.19
2.36
1.2
2.4
Economizer Fault Detection and
Diagnostics
Fault detection of the outdoor air damper will be
evaluated based on the commanded position of the
damper compared to the feedback position of the
damper. The damper is commanded to a position
based on a 2-10 Vdc signal.
N
No
otte
e:: In table below, ‘not economizing when should’
and ‘economizing when should not be’ have
been determined.
Table 17.
Economizer fault detection and diagnostics for units with or without Traq
™
™
Cooling
Request
Enthalpy
Decision
Indoor Fan -
(Ventilation
Requested)
Damper
Command VS
Feedback
Not
Economizing
When It
Should Be
Economizing
When It
Should Not Be
Outdoor
Air
Damper
Not
Modulat-
ing
Excessive
Outdoor
Air
N/A
N/A
N/A
Feedback - 10%
<= Setpoint <=
Fe 10%
(no fault)
(no fault)
(no fault)
(no fault)
N/A
N/A
OFF
Feedback High
FAULT
NO
(a)
N/A
ON
Feedback High
FAULT
N/A
ON
Feedback Low
FAULT
YES
Enabled
ON
Feedback High
FAULT
YES
Enabled
ON
Feedback Low
FAULT