56
RT-SVD03L-EN
•
Once the overflow condition has been cleared and
the input is OPEN for 6 seconds, all diagnostic
conditions will be cleared. The unit will return to
normal operation. Auto-reset clearing will occur
twice each time the unit is powered up. On the third
occurrence, the unit will initiate a lock-out and
require manual reset. If an auto-reset overflow
occurs once, but does not occur again for 72 hours,
the trip counter will reset allowing more auto-resets
to occur.
•
If overflow occurs during morning warm up (MWU)
or daytime warm up (DWU), the unit will not return
to warm up once diagnostic has been cleared.
However, if the zone temperature remains lower
than the initiate setpoint for DWU, the unit will
enter DWU upon reset.
•
If overflow trip occurs during a purge cycle on
dehumidification, purge will discontinue, but will
resume with a full 3 minute counter upon reset of
the trip.
•
If unit power cycle is used to reset a trip, the unit
will not carry forward any previous mode.
•
During manufacturing test mode, the overflow trip
indication will be reflected in the Modbus/BAS data
packets, but will not result in shutdown of any unit
components. The lockout trip counter will also be
continually reset to zero to allow unlimited trips
during this mode.
Fresh Air Measurement and
Control
Fresh air measurement and control function measures
the airflow through the outdoor air damper. Using this
measurement and comparing it with the desired
temperature, this function can vary the position of the
damper to keep the fresh air flow within the specified
range to maintain the desired temperature.
Service Test - Traq
™
control functionality will be active
during service test in all steps where the outside air
(OA) damper is held in the minimum position. This
would be all steps except the “economizing” step
which forces the damper open to 100%.
Sensor calibration adjustment - To make a minor
correction to the Traq
™
airflow reading that is
calculated internally by the ReliaTel
™
system an
adjustment pot is available on the RTVM. This pot can
be used to correct for static local factors such as
altitude. Variable factors such as drift, temperature,
humidity and other changing atmospheric conditions
are corrected as part of the conversion calculation.
Sequence for Setting Calibration
1. Adjust the minimum OA flow setpoint on the RTVM
to desired flow rate for minimum ventilation. Use
voltage vs CFM chart.
2. Initiate service test and step to the minimum
ventilation step. This will set the unit into a constant
ID fan speed and OA damper request to minimum
position. Minimum position will be from the Traq
™
calculation to maintain the OA flow at the setpoint
in
3. Wait for the damper position to settle to the desired
flow rate set by the setpoint, it should take about
one minute.
4. Measure OA flow rate via an air balancing
instrument.
5. Adjust calibration pot clockwise or counter-
clockwise to dial-in the flow to match instrument in
Table 15.
Design minimum OA flow setpoints
Design Min OA Flow
Setpoint (R130)
DCV Min OA Flow
Setpoint (R41)
Voltage
Reading
Airflow CFM
Airflow CFM
Voltage Vdc
1000
1000
0.2
1100
1100
0.22
1200
1200
0.24
1300
1300
0.26
1400
1400
0.28
1500
1500
0.3
1600
1600
0.32
1700
1700
0.34
1800
1800
0.36
1900
1900
0.38
2000
2000
0.4
2100
2100
0.42
2200
2200
0.44
2300
2300
0.46
2400
2400
0.48
2500
2500
0.5
2600
2600
0.52
2700
2700
0.54
2800
2800
0.56
2900
2900
0.58
3000
3000
0.6
3100
3100
0.62
3200
3200
0.64
3300
3300
0.66
3400
3400
0.68
3500
3500
0.7
3600
3600
0.72
3700
3700
0.74
3800
3800
0.76
3900
3900
0.78
4000
4000
0.8
4100
4100
0.82
4200
4200
0.84
4300
4300
0.86
4400
4400
0.88
4500
4500
0.9
4600
4600
0.92
4700
4700
0.94
4800
4800
0.96
4900
4900
0.98
5000
5000
1
5100
5100
1.01
5200
5200
1.02
Summary of Contents for ReliaTel
Page 174: ...174 RT SVD03L EN N No ot te es s...
Page 175: ...RT SVD03L EN 175 N No ot te es s...