RT-SVD03L-EN
39
ReliaTel
™
™
Temporary Operation
3 to 25 Tons
N
No
otte
e:: Does not apply to MZVAV.
Temporary comfort can be provided without a zone
sensor module or thermostat in place by using the
outdoor air sensor or a spare supply air/return air
sensor. How to do it: remove the sensor from the unit,
add enough thermostat wire to it so that it can be
placed in the return air stream, then connect the sensor
to J6-1 & J6-2.
After the permanent zone sensor or thermostat is in
place, the sensor must be removed from J6-1 & J6-2.
If the RTRM does not have a space temperature input
(J6-1, J6-2), or have a conventional thermostat input
(G, Y, W), the unit will not run (except in the test mode).
Temporary Sensor (Thermistor)
Attached to J6-1 and J6-2 Only
•
Continuous fan
•
Auto changeover
•
74°F cooling, 71°F heating
N
No
otte
e:: 27.5 to 50 tons - the outdoor air sensor
should not be used for this purpose.