12
RT-SVD03L-EN
COMM3/4 Communication Interface
Allows ICS communication between a ReliaTel
™
unit
and Trane
®
ICS systems as follows:
•
Tracer
®
100
™
series
•
Tracer
®
Summit
®
•
Tracker
®
•
ComforTrac
™
•
VariTrac
®
1 (Comfort Manager)
•
VariTrac
®
2 (Central Control Panel)
LonTalk
®
®
Communication Interface
General Information
The communication interface board allows ReliaTel
™
controls to communicate on a LonTalk
®
network at the
unit level. This product is intended to be installed by a
qualified system integrator properly trained and
experienced in LonTalk
®
networks. Network variables
are based on the LonMark® functional profile template.
The LCI-R utilizes a Free Topology transceiver FTT-10A.
The FTT-10A transceiver supports non-polarity
sensitive, free topology wiring, allowing the system
installer to utilize star, bus, and loop architecture.
Storage
When the LCI-R board must be stored for a period of
time prior to being installed, it must be protected from
the elements. The temperature of the storage location
should be between -40°C and 65.6°C (-40°F and 150°F)
and the relative humidity should be 10 to 90 percent,
non-condensing
Mounting and Wiring
The LCI-R board mounts directly in the unit control box.
Shipment and Inspection - LCI-R
The LCI-R kit includes the following items:
•
1 - LCI-R communications board
•
1 - Wire harness
•
4 - LCI-R board mounting screws
•
1 - Pop-in wire tie (BAYLTCI002*)
ReliaTel
™
™
BACnet
®
®
Communication
Interface (BCI-R)
General Information
The building automation and control network
(BACnet
®
and ANSI/ASHRAE Standard 135-2004)
protocol is a standard that allows building automation
systems or components from different manufacturers
to share information and control functions. The
BACnet
®
communication interface for ReliaTel
™
supports Trane
®
ReliaTel
™
rooftop units that function
as part of a BACnet
®
MS/TP communications network.
It allows ReliaTel
™
equipment to communicate with a
building automation system (BAS) by using BACnet
®
protocol over an RS-485 MS/TP communications link.
The BCI-R module implements all the required
BACnet
®
capabilities for a BACnet
®
Application
Specific Controller (B-ASC). This product is intended to
be installed by a qualified system integrator properly
trained and experienced in BACnet
®
networks. The
BCI-R supports three product families that use the
ReliaTel
™
controls platform: Precedent
™
, Voyager
™
,
and Odyssey
™
.
BCI-R Shipment and Inspection
BCI-R kits include the following items:
•
1 - BCI-R communications board
•
1 - Wire harness
•
4 - BCI-R board mounting screws
•
1 - Pop-in wire tie
Storage
When the BCI-R board must be stored for a period of
time prior to being installed, it must be protected from
the elements. The temperature of the storage location
should be between -40°C and 65.6°C (-40°F and 150°F)
and the relative humidity should be 10 to 90 percent,
non-condensing.