RT-SVD03L-EN
43
Table 7. RTOM discharge air heat setpoint
(continued)
Voltage (Vdc)
Setpoint (ºF)
2.25
140
2.26
141
2.28
142
2.29
143
2.3
144
2.32
145
2.33
146
2.34
147
2.36
148
2.37
149
2.4
150
Table 8. RTOM supply air reheat setpoint
Voltage (Vdc)
Setpoint (ºF)
0.002
65
0.169
65.5
0.317
66
0.395
66.5
0.552
67
0.672
67.5
0.785
68
0.915
68.5
1.028
69
1.114
69.5
1.206
70
1.275
70.5
1.365
71
1.445
71.5
1.525
72
1.61
72.5
1.683
73
1.766
73.5
1.822
74
1.887
74.5
1.94
75
1.998
75.5
2.064
76
2.118
76.5
2.175
77
2.196
77.5
2.234
78
2.275
78.5
2.318
79
2.368
79.5
2.415
80
Table 9. RTOM dehumidification setpoint
Voltage (Vdc)
Setpoint (%)
0.002
40
0.238
41
0.445
42
0.539
43
0.677
44
0.811
45
0.984
46
1.117
47
1.245
48
1.349
49
1.428
50
1.552
51
Table 9. RTOM dehumidification setpoint (continued)
Voltage (Vdc)
Setpoint (%)
1.625
52
1.745
53
1.824
54
1.853
55
1.929
56
1.978
57
2.07
58
2.136
59
2.184
60
2.259
61
2.268
62
2.324
63
2.397
64
Discharge Air (DA) Cooling -
Setpoint Lower Limit
Voyager
™
™
Light Commercial
eFlex
™
units will utilize a discharge air cool limit
potentiometer located on the RTOM (R-136).
N
No
otte
e:: This is not a DA setpoint, but a DA setpoint lower
limit.
Adjust the limit potentiometer by measuring the R-136
potentiometer test point loop to ground and comparing
it to the chart shown here.
N
No
otte
e:: 50° to 55°F for most applications.
Table 10.
Voyager
™
™
DA cool limit temp/voltage
°F
VDC
40
0.1
41
0.2
42
0.3
43
0.4
44
0.55
45
0.7
46
0.8
47
0.95
48
1.05
49
1.15
50
1.25
51
1.3
52
1.35
53
1.45
54
1.55
55
1.65
56
1.7
57
1.75
58
1.83
59
1.9
60
1.95
61
2
62
2.05
63
2.1
64
2.13
65
2.17
66
2.21
Summary of Contents for ReliaTel
Page 174: ...174 RT SVD03L EN N No ot te es s...
Page 175: ...RT SVD03L EN 175 N No ot te es s...