72
RT-SVD03L-EN
until space humidity > dehumidification setpoint - 2%
and the zone temperature is approaching either the
cooling or heating setpoint.
Idle Mode Operation
If unit is in idle mode and dehumidification conditions
are met, the compressors and supply fan will be started
to a predetermined point and run until the above
termination conditions are met.
Condenser Fan Control
For single compressor units with a VSPD compressor,
the unit will also be equipped with a variable speed
VSM condenser fan motor.
The condenser fan shall be controlled based on the
following tables:
Table 27.
Condenser fan control data 3 – 5 tons
OAT Condition
VSPD Comp.
Speed
3 Tons
4 Tons
5 Tons
RPM
% Cond.
Airflow
Duty
Cycle
RPM
% Cond.
Airflow
Duty
Cycle
RPM
% Cond.
Airflow
Duty
Cycle
OAT>95F
Min<Hz<Max
894
100%
73%
1013
100%
84%
1076
100%
89%
45F<OAT<90F
<23Hz
383
40%
29%
473
40%
37%
524
40%
41%
25Hz<Hz<50Hz
691
70%
56%
743
70%
60%
800
70%
65%
>52Hz
894
100%
73%
1013
100%
84%
1076
100%
89%
<40F
Startup
290
32%
21%
311
22%
23%
358
22%
27%
25F<OAT<40F
Min<Hz<Max && !
Startup
236
26%
16%
311
22%
23%
358
22%
27%
OAT<20F
Min<Hz<Max && !
Startup
236
26%
16%
311
22%
23%
358
22%
27%
Note:
A 2 Hz hysteresis around the VSPD compressor speed will be implemented when transitioning from high speed to low speed.
Table 28.
Condenser fan control data 6 – 10 tons
OAT Condition
VSPD Comp.
Speed
6 Tons
10 Tons
RPM
% Cond.
Airflow
Duty
Cycle
RPM
% Cond.
Airflow
Duty
Cycle
OAT>95F
Min<Hz<Max
1001
100
83%
1130
100%
94%
45F<OAT<90F
<48Hz
473
40
31%
532
40%
37%
50Hz<Hz<70Hz
733
70
56%
831
70%
65%
>72Hz
1001
100
83%
1130
100%
94%
25F<OAT<40F
Min<Hz<Max
312
22
16%
352
22%
20%
OAT<20F
Min<Hz<Max
312
22
16%
352
22%
20%
OAT Condition
VSPD Comp.
Speed
7.5 Tons
8.5 Tons
RPM
% Cond.
Airflow
Duty
Cycle
RPM
% Cond.
Airflow
Duty
Cycle
OAT>95F
Min<Hz<Max
1111
100%
92%
1116
100%
92%
45F<OAT<90F
<23Hz
465
40%
31%
465
40%
31%
25Hz<Hz<53Hz
790
70%
61%
790
70%
61%
>55Hz
1111
100%
92%
1116
100%
92%
25F<OAT<40F
Min<Hz<Max
300
22%
15%
300
22%
15%
OAT<20F
Min<Hz<Max
300
22%
15%
300
22%
15%
Note:
A 2Hz hysteresis around the VSP compressor speed will be implemented when transitioning from high
speed to low speed.