84
RT-SVD03L-EN
Table 42.
Voyager
™
™
& Precedent
™
™
gas/electric units 3 to 25 tons
Step
Mode
IDM
Econ
CPR1
CPR2
HT1
HT2
Mod Gas
ODM1
ODM2
1
Fan On
On/Low
(a)
Min
Off
Off
Off
Off
Off
Off
Off
2
Econ.
Open
Off
Off
Off
Off
Off
Off
Off
3
Cool 1
On/Low
Min
On
On
(b)
Off
Off
Off
On
(c)
4
Cool 2
On/Low
Min
On
On
(d)
Off
Off
Off
On
5
Cool 3
On/High
Min
On
On
Off
Off
Off
On
6
Reheat
On/High
Min
On
On
Off
Off
Off
On
7
Heat 1
/High
Min
Off
Off
On
Off
50%
Off
Off
8
Heat 2
On/High
Min
Off
Off
On
On
100%
Off
Off
Note:
Steps for optional accessories and modes not present in unit will be skipped.
(a)
With optional accessory
(b)
CPR2 ON during Cool 1 if configured for 3-step cooling; CPR1 OFF.
(c)
"Off" if OAT falls below 60°F, "On" if OAT rises above 65°F. During Reheat, if the unit is configured with 1 compressor, ODM2 is "Off" if the OAT falls below
70F, "On" if the OAT rises above 75F.
(d)
CPR2 OFF during Cool 2 on a 3-step cooling unit.
Table 43.
Voyager
™
™
& Precedent
™
™
electric/electric units 3 to 25 tons
Step
Mode
IDM
Econ
CPR1
CPR2
HT1
HT2
ODM1
ODM2
1
Fan On
On/Low
(a)
Min
Off
Off
Off
Off
Off
Off
2
Econ.
Open
Off
Off
Off
Off
Off
Off
3
Cool 1
Min
On
On
(b)
Off
Off
On
(c)
4
Cool 2
On/Low
Min
On
On
(d)
Off
Off
On
5
Cool 3
On/High
Min
On
On
Off
Off
On
6
Reheat
On/High
Min
On
On
Off
Off
On
7
Heat 1
On/High
Min
Off
Off
On
Off
Off
Off
8
Heat 2
On/High
Min
Off
Off
On
On
Off
Off
Note:
Steps for optional accessories and modes not present in unit will be skipped.
(a)
With optional accessory
(b)
CPR2 ON during Cool 1 if configured for 3-step cooling; CPR1 OFF.
(c)
"Off" if OAT falls below 60°F, "On" if OAT rises above 65°F. During Reheat, if the unit is configured with 1 compressor, ODM2 is "Off" if the OAT falls below
70F, "On" if the OAT rises above 75F.
(d)
CPR2 OFF during Cool 2 on a 3-step cooling unit.