RT-SVD03L-EN
89
Table 54.
CV Test modes 27.5 to 50 tons with reheat
Test
Step
Mode
Fan
Econ.
Exh
Fan
Power
Exh
Damper
Comp 1 Comp 2 Heat 1 Heat 2
Mod
Heat
Cool
Valve
Reheat
Valve
Reheat
Pump
Out
Ohms
1
Minimum
Ventilation
On
Min
Off
Min
Off
Off
Off
Off
0%
100%
0%
Off
2.2k
2
Economizer
Test Open
On
100%
On
100%
Off
Off
Off
Off
0%
100%
0%
Off
3.3k
3
Cool Stage 1
On
Min
Off
Min
On
(a)
Off
Off
Off
0%
100%
0%
Off
4.7k
4
Cool Stage 2
On
Min
Off
Min
Off
(b)
On
(a)(b)
Off
Off
0%
100%
0%
On
(c)
6.8k
5
Cool Stage 3
On
Min
Off
Min
On
On
Off
Off
0%
100%
0%
On
8.2k
6
Heat Stage 1
On
Min
Off
Min
Off
Off
On
Off
50%
100%
0%
Off
10k
7
Heat Stage 2
On
Min
Off
Min
Off
Off
On
On
100%
100%
0%
Off
15k
8
Reheat
On
Min
Off
Min
On
On
Off
Off
0%
50%
50%
Off
33k
9
Reset
Notes:
1
.
Steps for optional accessories and modes not present in unit will be skipped.
2
.
Economizer, Exhaust Fan, Power Exhaust Damper, Heat 1 & 2, Modulating Heat, Cool Valve, Reheat Valve, and Reheat Pumpout = with optional
feature.
3
.
The exhaust fan will turn on anytime the economizer damper position is equal to or greater than the exhaust fan setpoint. It will not turn off until
the economizer damper position is at exhaust enable setpoint - 10% or lower.
(a)
The condenser fans will operate any time a compressor is ON providing the outdoor air temperatures are within normal operating range.
(b)
27½ to 35 tons units have two stages of mechanical cooling. Both compressors run during cool stage two.
(c)
The reheat pumpout output will be energized whenever the reheat circuit (circuit 2 for 40 to 50 tons) is energized for cooling operation.
Table 55.
Test mode states for Voyager
™
™
Commercial traditional VAV units with modulating dehumidification and
staged heat
Test
Step
Mode
Fan
VFD
Command
Econ.
Comp
1
Comp
2
Comp
3
Heat 1 Heat 2 Pumpout
Cool
Valve
Reheat
Valve
VAV
Box
1
VFD SIGNAL
100%
OFF
100%
(10VDC)
CLOSED
OFF
OFF
OFF
OFF
OFF
OFF
100%
0%
ON
2
VFD SIGNAL
0%
OFF
0% (0 VDC) CLOSED
OFF
OFF
OFF
OFF
OFF
OFF
100%
0%
ON
3
MIN VENT
ON
IN-
CONTROL
MIN
OFF
OFF
OFF
OFF
OFF
OFF
100%
0%
ON
4
ECON TEST
OPEN
ON
IN-
CONTROL
OPEN
OFF
OFF
OFF
OFF
OFF
OFF
100%
0%
ON
5
COOL 1
ON
IN-
CONTROL
MIN
ON
OFF
OFF
OFF
OFF
IN-
CONTROL
100%
0%
ON
6
COOL 2
ON
IN-
CONTROL
MIN
ON
ON
OFF
OFF
OFF
IN-
CONTROL
100%
0%
ON
7
COOL 3
ON
IN-
CONTROL
MIN
ON
ON
ON
OFF
OFF
IN-
CONTROL
100%
0%
ON
8
REHEAT
ON
IN-
CONTROL
MIN
ON
ON
ON
OFF
OFF
IN-
CONTROL
50%
50%
ON
9
HEAT 1
ON
IN-
CONTROL
MIN
OFF
OFF
OFF
ON
OFF
OFF
100%
0%
ON
10
HEAT 2
ON
IN-
CONTROL
MIN
OFF
OFF
OFF
ON
ON
OFF
100%
0%
ON
11
RESET
Notes:
1
.
2 & 3 stage standard efficiency units: For Traditional VAV units, the VFD Command when “In-Control” will be controlled based on supply air
pressure requirements. For SZVAV units, the VFD command will be at discrete points during Test Mode.
2
.
2 & 3 stage standard efficiency units: For 27½ to 35 ton units, both compressors will be energized during the Cool 2 Step. For 40-50T units,
only Compressor 2 will be energized during the Cool 2 Step.
3
.
2 & 3 stage standard efficiency units: The reheat pumpout relay will be energized any time the reheat circuit is energized in active Cooling
Mode.
4
.
2 & 3 stage standard efficiency units: For units with Statitrac™ installed, the exhaust damper will track the Economizer position during
Service Test Mode and the Exhaust Fan will be energized once the economizer rises above the exhaust enable setpoint.
5
.
2 & 3 stage standard efficiency units: Heating will not be energized during Service Test until the 6 minute VAV box ON timer has expired.
6
.
5 stage high efficiency units: Compressor 1 is the smaller compressor on the circuit.
7
.
5 stage high efficiency units: Condenser fans are controlled as defined for normal operation.
8
.
5 stage high efficiency units: Exhaust fan operates as defined for normal operation based on economizer position.
9
.
5 stage high efficiency units: When compressor 1 is energized with either C1, C2, or with both for 30 minutes continuously, C3 will be
required to de-energize for 30 seconds.