RT-SVD03L-EN
83
Table 40.
Precedent
™
™
6 to 10 tons high efficiency heat pump SZVAV (w/ unloading compressor)
Mode
C1
Unload-
ed
C2
Loaded
EMAIR
Fan
Spd
(Fixed
Spd)
CFB
Heat 1
Heat 2
SOV 1
Econ
S Fan
S Fan
Speed
Com-
mand
(ECM)
Resistance
1. Fan On
Off
Off
Off
Off
Off
Off
Off
Min.
On
68%
2.2K
2. Econ
Off
Off
Off
Off
Off
Off
On
100%
On
68%
3.3K
3. Cool 1
On
Off
Off
Norm
(a)
Off
Off
On
Min.
On
68%
4.7K
4. Cool 2
On
On
Off
Norm
Off
Off
On
Min.
On
68%
6.8K
5. Cool 3
On
On
On
Norm
Off
Off
On
Min
On
100%
8.2K
6. Heat 1
On
On
Off
Off
Off
Off
Off
Min.
On
68%
(b)
10K
7. Heat 2
On
On
On
Off
Off
Off
Off
Min.
On
100%
15K
8. Heat 3
On/Off
(c)
Off
On
Off
Off
Min.
On
100%
22K
9. Heat 4
On/Off
Off
On
On
Off
Min.
On
100%
27K
10. Defrost
On
On
On
Off
On
Off
On
Min.
On
100%
33K
11. Em Heat
Off
Off
Off
Off
On
On
Off
Min.
On
100%
47K
(a)
Normal Condenser Fan staging shall remain in effect during Service Test mode
(b)
Depends on if Heat mode has a higher maximum fan speed than cool mode
(c)
Dependent on auxiliary heat being Electric Heat (On) or Gas Heat (Off)
Table 41.
Precedent
™
™
6 to 10 tons high efficiency heat pump MZVAV (w/ unloading compressor)
Mode
C1
Unload-
ed
C2
Loaded
EMAIR
Fan
Spd
(Fixed
Spd)
CFB
Heat 1
Heat 2
SOV 1
Econ
S Fan
S Fan
Speed
Com-
mand
(ECM)
Resistance
1. IGV/VFD Open
Off
Off
Off
Off
Off
Off
Off
Closed
Off
Min Speed
NA
2. IGV/VFD Close
Off
Off
Off
Off
Off
Off
Off
Closed
Off
Min Speed
NA
3. Fan On
Off
Off
Off
Off
Off
Off
Off
Min.
On
Min Speed
2.2K
4. Econ
Off
Off
Off
Off
Off
Off
On
100%
On
Min Speed
3.3K
5. Cool 1
On
Off
Off
Norm
(a)
Off
Off
On
Min.
On
Min Speed
4.7K
6. Cool 2
On
On
Off
Off
Off
On
Min.
On
In Control
(b)
6.8K
7. Cool 3
On
On
On
Off
Off
On
Min
On
In Control
8.2K
8. Heat 1
On
On
Off
Off
Off
Off
Off
Min.
On
100%
(c)
10K
9. Heat 2
On
On
On
Off
Off
Off
Off
Min.
On
15K
10. Heat 3
On/Off
(d)
On/Off
Off
On
Off
Off
Min.
On
22K
11. Heat 4
On/Off
On/Off
Off
On
On
Off
Min.
On
27K
12. Defrost
On
On
On
Off
On
Off
On
Min.
On
100%
33K
13. Em Heat
Off
Off
Off
Off
On
On
Off
Min.
On
100%
47K
(a)
Normal Condenser Fan staging shall remain in effect during Service Test mode
(b)
Supply Fan Speed controlled to duct static pressure
(c)
Depends on if Heat mode has a higher maximum fan speed than cool mode
(d)
Dependent on auxiliary heat being Electric Heat (On) or Gas Heat (Off)