RT-SVD03L-EN
171
Table 106.
VAV setpoints (continued)
Supply Air
Pressure
Setpoint
Supply Air
Cooling
Setpoint
Supply Air
Reset
Amount
Supply Air
Pressure
Deadband
Morning
Warm-up
Setpoint
Supply Air
Reset
Setpoint
Outdoor
Supply Air
Reset
Setpoint
Zone or
Return Air
RTAM
Supply Air
Heat
Setpoint
J7-1,2
J7-3,4
J7-5,6
J7-7,8
J7-9,10
J7-11,12
J7-11,12 J7 - 13, 14
Resist-
ance
(Ohms)
DC Volts
WC
Deg F
Deg F
WC
Deg F
Deg F
Deg F
Deg F
960
2.45
2.5
80
20
1
90
100
90
150
970
2.46
2.5
80
20
1
90
100
90
150
980
2.47
2.5
80
20
1
90
100
90
150
990
2.49
2.5
80
20
1
90
100
90
150
1000
2.5
2.5
80
20
1
90
100
90
150
Notes:
1
.
Supply air pressure setpoint valid range is 0.3”-2.5”.
2
.
Supply air pressure deadband valid range is 0.2”-1”.