applications with extreme winds could require
mounting the sensor in an area less affected by wind.
BAYSENS021* Setpoint Input
This chart lists setpoint /voltage/resistance for the VAV
supply air cooling setpoint on the RTRM module. The
chart can be used for troubleshooting units that have a
remote setpoint at this input.
The typical remote setpoint input device is a
BAYSENS021* zone sensor.
The connection points are RTRM J6-2 and RTRM J6-3.
If a remote setpoint is used, clip jumper R69 on the
RTAM module. If the jumper is not clipped, the unit will
ignore the RTRM setpoint.
N
No
otte
e:: A remote setpoint can also be applied to the
RTAM supply air cooling setpoint input.
However, the RTAM inputs use different
temperature/ resistance inputs. See VAV setpoint
inputs for input values.
Table 105.
Supply air cooling setpoint
Supply Air
Cooling
Setpoint (°F)
Resistance
(ohms)
DC Volts
40
1084
2.6
41
1065
2.58
42
1045
2.56
43
1026
2.53
44
1006
2.51
45
987
2.48
46
967
2.46
47
948
2.43
48
928
2.41
49
909
238
50
889
2.35
51
870
2.33
52
850
2.3
53
831
2.27
54
812
2.24
55
792
2.21
56
773
2.18
57
753
2.15
58
734
2.12
59
714
2.08
60
695
2.05
61
675
2.02
62
656
1.98
63
636
1.94
64
617
1.91
65
597
1.87
66
578
1.83
67
558
1.79
68
539
1.75
69
519
1.71
70
500
1.67
71
481
1.62
72
461
1.58
73
442
1.53
74
422
1.48
75
403
1.44
76
383
1.39
Table 105.
Supply air cooling setpoint (continued)
Supply Air
Cooling
Setpoint (°F)
Resistance
(ohms)
DC Volts
77
364
1.33
78
344
1.28
79
325
1.23
80
305
1.17
This chart lists setpoint/voltage/resistance for VAV
setpoints on the RTAM module in the control
compartment. The chart can be used for
troubleshooting the RTAM module or for applying a
remote setpoint to the unit.
Each setpoint can be provided remotely by applying
the appropriate resistance as shown in the table after
cutting the resistor next to the setpoint knob. See
.
Remote Setpoint Inputs on RTAM J7
J7-1, 2 Supply air pressure Setpoint
J7-3, 4 Supply air cooling setpoint
J7-5, 6 Supply air reset amount
J7-7, 8 Supply air pressure Deadband
J7-9, 10 Morning warm-up setpoint
J7-11, 12 Supply air reset setpoint
J7-13, 14 Supply air heating setpoint
Figure 106.
RTAM module
Static
pressure
setpoint
Static
pressure
deadband
For remote deadband cut
this jumper
Reset
setpoint
Supply Air Heating
Setpoint
R66
Reset
amount
Supply air
cooling
setpoint
Morning
warmup
setpoint
R63
R68
R69
R67
R64
1 2 3 4 5 6 7 8 9 10 11 12
Remote setpoint
terminal strip
12345
SW1
Supply Air (Static) Pressure S.P.
DIP switch
1
I
G
U
C
o
n
f
i
g
R
e
s
e
t
S
e
l
e
c
t
D
W
U
E
n
a
b
l
e
VAV w / o I G V
I G V - O F F O F F
V F D - O N O F F
1
2
N o R e s e t O F F O F F
R e t u r n A i r O F F O N
Zo n e Te m p O N O F F
O u t d o o r A i r O N O N
3
4
5
D W U D i s a b l e O F F
D W U E n a b l e O N
ON
Supply Air Cooling Setpoint
Supply Air Reset Amount
Supply Air (Static) Pressure Deadband
Morning Warmup Setpoint
Supply Air Reset Setpoint
O F F O N
O N O N
2
3
4
5
SW1
R 75
13 14
Supply Air Heating Setpoint
J5
1
2
LTB-5 (25.5 to 50)
Changeover input (VAV only)
For remote setpoint cut this jumper:
Supply air pressure setpoint R64
Supply air cooling setpoint R69
Supply air heating setpoint R75
Supply air reset amount R68
Supply air pressure Deadband R67
Morning warm-up setpoint R63
Supply air reset setpoint R66