Communications group
C301 [Language]
Selects the language displayed by the remote communications option.
Options
1
"English" (Default)
2
"Second language" (Reserved)
C302 [Comm data rate]
Related Parameter(s): d015
Sets the serial port rate for the RS485 (DSI) port.
Important:
Power to drive must be cycled before changes will affect drive operation.
Options
0
1200 Baud
1
2400 Baud
2
4800 Baud
3
9600 Baud (Default)
4
19.2k Baud
5
38.4k Baud
C303 [Comm node addr]
Related Parameter(s): d015
Sets the drive node address for the RS485 (DSI) port if using a network connection.
Important:
Power to drive must be cycled before any changes will affect drive operation.
Values
Default:
100
Min/Max:
1/247
Display:
1
C304 [Comm loss action]
Related Parameter(s): d015, P107, C305
Selects the drive’s response to a loss of the communication connection or excessive communication
errors.
Options 0
"Fault" (Default)
Drive will fault on an F81 Comm Loss and coast to stop.
1
"Coast to stop"
Stops drive via coast to stop.
2
"Stop"
Stops drive via P107 [Stop Mode] setting.
3
"Continue last"
Drive continues operating at communication commanded speed
saved in RAM.