ILVFE-series
user manual
45
t212 [Anlg in 0-10V Hi]
Related Parameter(s): d020, P105, P108, t201, t202
Sets the analog input level that corresponds to P105 [Maximum Freq] if a 0-10V input is used by P108
[Speed reference].
Analog inversion can be accomplished by setting this value smaller than t211 [Anlg in 0-10V Hi] or by
setting t201 - t202 [Digital inx sel] to option 15 “Anlg invert”.
Values
Default:
100.0 %
Min/Max:
0.0/100.0 %
Display:
0.1 %
t213 [Anlg in 4-20mA Lo]
Related Parameter(s): d021, P104, P108, t201, t202
Sets the analog input level that corresponds to P104 [minimum freq] if a 4-20mA input is used by P108
[Speed reference].
Analog inversion can be accomplished by setting this value larger than t214 [Anlg in 0-10V Hi] or by
setting t201 - t202 [Digital inx sel] to option 15 “Anlg invert”.
Values
Default:
0.0 %
Min/Max:
0.0/100.0 %
Display:
0.1 %
t214 [Anlg in 4-20mA Hi]
Related Parameter(s): d020, P105, P108, t201, t202
Sets the analog input level that corresponds to P105 [Maximum freq] if a 4-20mA input is used by
P108 [Speed reference].
Analog inversion can be accomplished by setting this value smaller than t213 [Anlg in 0-10V Hi] or by
setting t201 - t202 [Digital inx sel] to option 15 “Anlg invert”.
Values
Default:
100.0 %
Min/Max:
0.0/100.0 %
Display:
0.1 %
Summary of Contents for ILVFE-1W0075