ILVFE-series
user manual
59
A453 [Boost select]
Related parameter(s): d004, P101, P102
Sets the boost voltage (% of P101 [Motor NP Volts]) and redefines the Volts per Hz curve.
(1)
(1)
Drive may add additional voltage unless option 5 is selected.
Options 1
"30.0, VT"
Variable torque
2
"30.0, VT"
3
"30.0, VT"
4
"30.0, VT"
5
"0.0 no IR"
Constant torque
6
"0.0"
7
"2.5, CT" (Default for 3.7, 5.5, 7.5 &11 kW)
8
"5.0, CT" (Default)
9
"7.5, CT"
10
"10.0, CT"
11
"12.5, CT"
12
"15.0, CT"
13
"17.5, CT"
14
"20.0, CT"