A424 [DC brake time]
Related Parameter(s): P107, A425
Sets the length of time that DC brake current is “injected” into the motor. Refer to parameter A425 [DC
brake level].
Values
Default:
0.0 Secs
Min/Max:
0.0/99.9 Secs (a setting of 99.9= continous)
Display:
0.1 Secs
A425 [DC brake level]
Related Parameter(s): P107, A418
Defines the maximum DC brake current, in amps, applied to the motor when P107 [Stop Mode] is set
to either “Ramp” or “DC Brake”.
Values
Default:
Drive rated amps x 0.05
Min/Max:
0.0/(Drive rated amps x 1.8)
Display:
0.1 Amps
Attention:
If a hazard of injury due to movement of equipment or material exists, an
auxiliary mechanical braking device must be used.
Attention:
This feature should not be used with synchronous or permanent magnet
motors. Motors may be demagnetized during braking.