40
ILVFE-series
user manual
P107 [Stop mode]
Related Parameter(s): P106, A418, A425, A427, C304
Active stop mode for all stop sources [e.g. keypad, run forward (I/O Terminal 02), run reverse (I/O
Terminal 03), RS485 port] except as noted below.
Important:
I/O Terminal 01 is always a coast to stop input except when P106
[Start Source] is set for
“3-Wire” control. When in three wire control, I/O Terminal 01 is controlled by P107
[Stop Mode].
Options
0
“Ramp, CF”
(1)
(Default)
Ramp to Stop. “Stop” command clears active fault.
1
“Coast, CF”
(1)
Coast to Stop. “Stop” command clears active fault.
2
“DC Brake, CF”
(1)
DC Injection Braking Stop. “Stop” command clears active
fault.
3
“DCBrkAuto,CF”
(1)
DC Injection Braking Stop with Auto Shutoff.
•
Standard DC Injection Braking for value set in A424
[DC Brake Time].
or
•
Drive shuts off if the drive detects that the motor is
stopped.
“Stop” command clears active fault.
4
“Ramp”
Ramp to Stop.
5
“Coast”
Coast to Stop.
6
“DC Brake”
DC Injection Braking Stop.
7
“DC BrakeAuto”
DC Injection Braking Stop with Auto Shutoff.
•
Standard DC Injection Braking for value set in A424
[DC Brake Time].
or
•
Drive shuts off if current limit is exceeded.
(1)
Stop input also clears active fault.