6.6.3 DNP3.0 Point List
The following table identifies for each data type, the data points available in the device.
Binary Input Points Slave >> Master
Static (Steady-State) Object Number:
1
Change Event Object Number: 2
Static Variation reported when variation 0 requested:
1 (Binary Input 2 without status)
Change Event Variation reported when variation 0 requested:
3 (Binary Input Change with Time)
Event
Class
Point
Index
Default
Group
Default
Variable
Name/Description
Circuit Breaker Monitor
1
0
2
2
Breaker Is Open
1
1
2
2
A-B Logic Failure Alarm Active
1
2
2
2
Contact Life Warning Active Phase A
1
3
2
2
Contact Life Warning Active Phase B
1
4
2
2
Contact Life Warning Active Phase C
1
5
2
2
Contact Life Danger Alarm Active Phase A
1
6
2
2
Contact Life Danger Alarm Active Phase B
1
7
2
2
Contact Life Danger Alarm Active Phase C
1
8
2
2
Trip Time Alarm Active
1
9
2
2
Arc Time Alarm Active Phase A
1
10
2
2
Arc Time Alarm Active Phase B
1
11
2
2
Arc Time Alarm Active Phase C
1
12
2
2
Clearing Time Alarm Active Phase A
1
13
2
2
Clearing Time Alarm Active Phase B
1
14
2
2
Clearing Time Alarm Active Phase C
1
15
2
2
Travel Time Alarm Active
1
16
2
2
Closing Time Alarm Active
1
17
2
2
Operation Count Alarm Active
1
18
2
2
No-Operations Alarm Active
1
19
2
2
Restrike Alarm Active Phase A
1
20
2
2
Restrike Alarm Active Phase B
1
21
2
2
Restrike Alarm Active Phase C
SF
6
Monitor
1
22
2
2
Sensor Malfunction Alarm Active
1
23
2
2
Low Density Alarm Active
1
24
2
2
Trend Alarm Active
1
25
2
2
CT Failure Alarm Active Phase A
1
26
2
2
CT Failure Alarm Active Phase B
1
27
2
2
CT Failure Alarm Active Phase C
30
5
Default Static Analog
32
5
Default Event Analog
20
1
Default Static Counter
22
1
Default Event Counter
1
2
Default Static Binary
2
2
Default Event Counter