![Incon OPTImizer 2 User Manual Download Page 56](http://html.mh-extra.com/html/incon/optimizer-2/optimizer-2_user-manual_2051173056.webp)
56
Category: The alarm Category identifies what class the
alarm belongs to: System, Circuit Breaker
Monitoring (CBM) or SF6 Monitoring. The prefix
“alc” is used to indicate that it is a Category code.
Type:
The alarm Type indicates the severity of the
alarm condition: Warning, Alarm or Failure. The
prefix “alt” is used to indicate that it is a Type
code
Device: The alarm Device and Data combine to indicate
the location of the alarm condition. The prefix
“ald” is used to indicate that it is a Device code.
Device code “
aldChannelCBM
” indicates that
the alarm relates to one of the circuit breaker
phases.
Device code “
aldChannelSF6
” indicates
that the alarm relates to one of the SF
6
input
channels.
Device code “
aldNone
” indicates that the alarm
is a non-phase or non-channel related alarm.
Data:
The Device Data indicates which CB phase or
SF
6
input channel caused the alarm;
0 = None;
1 = A; 2 = B; 3 = C
.
State:
The State code indicates the present state of
the alarm: Active or Inactive. The prefix “als” is
used to indicate that it is a State code.
Occurred: The report indicates the date and time the alarm
occurred.
Cleared: The report indicates the date and time the alarm
was cleared. Alarms that are presently in the
active state will not have a cleared date and
time.
Application Event History Report
The Application Event History Report consists of: Code;
Category; Device; Data; (Date & Time) Occurred
Code:
This Code is an abbreviation for the description
of the Application Event. The prefix “ae” is used
to indicate that it is an Application Event code.
The table below gives the description of each
Application Event Code:
Category: The Application Event Categories are the same
as Alarm Categories.
Device: The Application Event Devices are the same as
Alarm Devices.
Data:
The Application Event Data are the same as
Alarm Data.
Occurred: The report indicates the date and time the
Application Event occurred.
Code:
Description:
Cause:
aeConfigurationChanged Configuration Changed
One or more program setting has changed
aeSystemTimeChanged
System Time Changed
The system clock time or date has changed
aeCircuitBreakerOpened Circuit Breaker Opened
The CB was closed and now is open
aeCircuitBreakerClosed
Circuit Breaker Closed
The CB was open and now is closed
aeSF6DensityIncrease
Density Increase Detected
SF
6
gas has been added or density sensor malfunction
Table 9: Application Event Codes