![Incon OPTImizer 2 User Manual Download Page 66](http://html.mh-extra.com/html/incon/optimizer-2/optimizer-2_user-manual_2051173066.webp)
66
6.6 DNP3.0
The following table provides a “Device Profile Document” in the standard format defined in the
DNP3 Subset Definitions Document. While it is referred to in the DNP3 Subset Definitions as a
“Document,” it is only a component of a total interoperability guide. This table in combination with
the Implementation Table should provide a complete interoperability/configuration guide for the
OPTI
mizer
2
.
6.6.1 Device Profile Document
DNP V3.0
Device Profile Document
(Also see the DNP Implementation Table, beginning on page 68)
Vendor Name:
Franklin Fueling Systems, Inc.
INCON Power Reliability Systems
Device Name:
OPTImizer
2
Highest DNP Level Supported:
For Requests:
Level 2
For Responses:
Level 2
Device Function:
1
Master
g
Slave
Notable objects, functions, and/or qualifiers supported in addition to the Highest DNP Levels Supported (the
complete list is described in the Implementation Table):
NONE
Maximum Data Link Frame Size (octets):
Transmitted:
292
Received:
292
Maximum Application Fragment Size (octets):
Transmitted: Fixed at 4096
Received: Fixed at 4096
Maximum Data Link Re-tries:
1
None
1
Fixed
g
Configurable from 0 to 255
Maximum Application Layer Re-tries:
1
None
g
Configurable from 0 to 65535
Requires Data Link Layer Confirmation:
1
Never
1
Always
g
Sometimes
1
Configurable
Requires Application Layer Confirmation:
1
Never
1
Always
g
Sometimes
1
Configurable
Timeouts while waiting for:
Data Link Confirm:
1
None
g
Fixed at 1 sec.
1
Variable
1
Configurable
Complete Appl. Fragment
1
None
g
Fixed at 5 sec.
1
Variable
1
Configurable
Application Confirm:
1
None
g
Fixed at 5 sec.
1
Variable
1
Configurable
Complete Appl. Response:
1
None
g
Fixed at 5 sec.
1
Variable
1
Configurable