268
ifm
System Manual
ecomat
mobile
SmartController (CR2500, CR2502) V05
Controller functions in the ecomatmobile controller
Functions for controllers
Recommended setting
►
Select TN according to the time characteristics of the system:
fast system = small TN
slow system = large TN
►
Slowly increment KP gradually, up to a value at which still definitely no fluctuation will occur.
►
Readjust TN if necessary.
►
Add
d
ifferential component only if necessary:
Select a TV value approx. 2...10 times smaller than TN.
Select a KD value more or less similar to KP.
Note that the maximum control deviation is + 127. For good control characteristics this range should
not be exceeded, but it should be exploited to the best possible extent.