PWM in the ecomatmobile controller
Hydraulic control in PWM
199
Examples NORM_HYDRAULIC
Parameter
Case 1
Case 2
Case 3
Upper limit value input XH
100
100
2000
Lower limit value input XL
0
0
0
Upper limit value output YH
2000
0
100
Lower limit value output YL
0
2000
0
Non standardised value X
20
20
20
Standardised value Y
400
1600
1
Case 1:
Input with relatively coarse resolution.
Output with high resolution.
1 X increment results in 20 Y increments.
Case 2:
Input with relatively coarse resolution.
Output with high resolution.
1 X increment results in 20 Y increments.
Output signal is inverted as compared to the input signal.
Case 3:
Input with high resolution.
Output with relatively coarse resolution.
20 X increments result in 1 Y increment.