SmartController (CR2500, CR2502) V05
More functions in the ecomatmobile controller
Adapting analogue values
255
Parameters of the function inputs
Name
Data type Description
X
WORD
current input value
XH
WORD
upper limit of input value range
XL
WORD
lower limit of input value range
YH
WORD
upper limit of output value range
YL
WORD
lower limit of output value range
Parameters of the function outputs
Name
Data type Description
Y WORD
normalised
value
Example 1
lower limit value input
upper limit value input
lower limit value output
upper limit value output
0
100
0
2000
XL
XH
YL
YH
then the function converts the input signal for example as follows:
from X =
50 0 100
75
to Y =
1000 0 2000
1500
Example 2
lower limit value input
upper limit value input
lower limit value output
upper limit value output
2000
0
0
100
XL
XH
YL
YH
then the function converts the input signal for example as follows:
from X =
1000 0 2000
1500
to Y =
50 100 0 25