55
FaULT FINDINg
F
a
UL
T FINDIN
g
F
a
UL
T FINDIN
g
F
a
UL
T FINDIN
g
F
a
UL
T FINDIN
g
F
a
UL
T FINDIN
g
Ideal Logic Code Combi -
Installation and Servicing
81 aLTERNaTINg ‘L’ aND ‘3’ - NO WaTER FLOW LOCKOUT
Is the Boiler and CH System filled with water and all
isolation and radiator valves open?
YES
Fill and vent the system and open all
isolation valves, reset the boiler.
Reset the boiler. Is the Flow/Return Differential
across the Boiler in excess of 30°C?
NO
Check pump connection and check
that the Pump is rotating freely. Is the
Differential now below 20°C?
YES
NO
Check the Flow and Return Thermistors
(Refer to Frame 53)
Check resistance using a suitable multimeter
connected across the thermistor’s terminal pins
At 25
o
C expect
9,700 - 10,300
Ohms
At 60
o
C expect
2,400 - 2,600
Ohms
At 85
o
C expect
1,000 - 1,100 Ohms
Replace the Pump
NO
OK
YES
Check the No Water Flow Thermistor and connections
(Refer to Frame 73).
Check resistance using a suitable multimeter
connected across the thermistor’s terminal pins
At 25
o
C expect
9,700 - 10,300
Ohms
At 60
o
C expect
2,400 - 2,600
Ohms
At 85
o
C expect
1,000 - 1,100
Ohms
Does the boiler now work OK?
82 aLTERNaTINg ‘L’ aND ‘6’ - FaLsE FLaME LOCKOUT
Reset the boiler, does Boiler Work OK?
NO
Check routing and integrity of internal boiler
wiring is OK. Check condition of Flame Sense
Electrode and replace if deteriorated.
Separate the flame detection electrode in-line
connector. Is there continuity between the terminals
pins connected to the electrode?
YES
Replace Flame Detection Electrode
YES
NO
Check routing and integrity of internal boiler wiring.
83 aLTERNaTINg ‘F’ aND ‘1’ - LOW WaTER pREssURE
Are the Boiler and CH System filled with water and
all isolation and radiator valves open (check pressure
gauge is between 1 to 1.5 bar)?
NO
Fill and vent the system and open all isolation valves
YES
Are connections on water pressure sensor secure?
NO
REsET pROCEDURE
- To reset boiler, turn mode knob to reset position and immediately turn knob back to required setting.
REsET pROCEDURE
- To reset boiler, turn mode knob to reset position and immediately turn knob back to required setting.
NO
Re-fit connections
Replace water pressure sensor
YES
206279-1.indd 55
06/01/2011 09:10:49
Summary of Contents for LOGIC Code Combi 26
Page 2: ...2 Ideal Logic Code Combi Installation and Servicing ...
Page 61: ......