Attention:
Ensure
that
you
comply
with
the
following
requirements
for
uninterruptible
power
supplies:
v
Each
uninterruptible
power
supply
should
be
connected
to
a
separate
branch
circuit.
v
A
UL
listed
15
A
circuit
breaker
must
be
installed
in
each
branch
circuit
that
supplies
power
to
the
uninterruptible
power
supply.
v
If
a
rack
power
distribution
unit
is
used,
each
uninterruptible
power
supply
must
be
connected
to
a
separate
power
distribution
unit.
v
The
voltage
supplied
to
the
uninterruptible
power
supply
must
be
200–240
V
single
phase.
v
The
frequency
supplied
must
be
between
50
and
60
Hz.
Note:
If
the
uninterruptible
power
supply
is
cascaded
from
another
uninterruptible
power
supply,
the
source
uninterruptible
power
supply
must
have
at
least
3
times
the
capacity
per
phase
and
the
total
harmonic
distortion
must
be
less
than
5%
with
any
single
harmonic
being
less
than
1%.
The
uninterruptible
power
supply
also
should
have
input
voltage
capture
that
has
a
slew
rate
faster
than
3
Hz
per
second
and
1
msec
glitch
rejection.
10.
All
front
panel
indicators
of
the
uninterruptible
power
supply
flash
for
a
short
time
while
the
uninterruptible
power
supply
runs
a
self
test.
When
the
test
is
complete,
the
mode
indicator
1
flashes
to
show
that
the
uninterruptible
power
supply
is
in
standby
mode
(see
Press
and
hold
the
uninterruptible
power
supply
on
switch
2
until
you
hear
the
uninterruptible
power
supply
beep
(approximately
one
second).
The
mode
indicator
stops
flashing
and
the
load
level
indicators
display
the
percentage
of
load
that
is
being
supplied
by
the
uninterruptible
power
supply.
The
uninterruptible
power
supply
is
now
in
normal
mode,
and
is
charging
its
battery.
If
the
mode
indicator
is
flashing
red
and
the
alarm
is
sounding,
the
voltage
range
alarm
setting
might
not
be
correct.
When
a
SAN
Volume
Controller
is
connected
to
the
uninterruptible
power
supply,
the
SAN
Volume
Controller
automatically
adjusts
the
voltage
range
settings.
Take
no
action
for
this
alarm
condition
unless
it
persists
for
more
than
five
minutes
after
a
SAN
Volume
Controller
has
been
connected
to
this
uninterruptible
power
supply
and
powered
on.
11.
Repeat
this
entire
procedure
to
install
the
other
uninterruptible
power
supply.
+ -
+ -
25%
100%
2
1
1
Figure
26.
Power
switch
and
indicators
of
the
uninterruptible
power
supply
Chapter
4.
Installing
the
uninterruptible
power
supply,
the
master
console,
and
the
SAN
Volume
Controller
23
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Summary of Contents for TotalStorage
Page 1: ...IBM TotalStorage SAN Volume Controller Installation Guide V ersion 1 2 0 SC26 7541 02...
Page 2: ......
Page 3: ...IBM TotalStorage SAN Volume Controller Installation Guide V ersion 1 2 0 SC26 7541 02...
Page 22: ...xx Installation Guide...
Page 36: ...14 Installation Guide...
Page 58: ...36 Installation Guide...
Page 74: ...52 Installation Guide...
Page 80: ...58 Installation Guide...
Page 84: ...62 Installation Guide...
Page 89: ......
Page 90: ...Part Number 64P8120 Printed in USA SC26 7541 02 1P P N 64P8120...
Page 91: ...Spine information IBM TotalStorage SAN Volume Controller Installation Guide Version 1 2 0...