Manual
ibaBM-DP
60
Issue 1.7
Note
When clicking on the header of a column, the settings of the lines below are completed
automatically.
Example:
You want to set a different data type beginning with a certain row: Change the data type
in the first row of the chosen rows and then click on the header "Data type". The data type
will be changed automatically in all lines below.
If you want to calculate the addresses automatically depending on the selected data type:
Set the right address in the first row (usually 0) and then click on the "Address" header.
Now, the addresses are filled in sequential order taking into account the data type you
have selected.
Similar functions are also available for the other columns.
Thus, the effort for configuration can be reduced.
13.
If required, select a scaling value of the signals in the columns "Gain" and "Offset"
for converting them into physical units.
14.
For digital signals on the “Digital" tab, proceed as shown above. You do not need to
enter a data type. The address offset is given in 1 byte steps. The signals are ad-
dressed by the bit numbers 0 … 7.
15. Sniffing on the PROFIBUS ("Sniffer" module)
With this module, you generate a sniffer on the bus that is able to record the existing
telegram traffic between master and slaves within a PROFIBUS system.
For a detailed description of the "Sniffer" module, please see chapter 10.3.2.