Manual
ibaBM-DP
164
Issue 1.7
17
Technical data
17.1 Main Data
Manufacturer
iba AG, Germany
Order No.
13.121001
Description
PROFIBUS bus monitor
PROFIBUS interfaces
DP connections
2 x 9-pin D-Sub connector (Bus0, Bus1)
Data transfer rates
9.6 kbit/s to 12 Mbit/s
DP slaves (can be configured as
active slaves on the device)
Max. 8, can be distributed as required on both PROFIBUS
lines (can be extended on request)
Address range of the slaves
1 to 126
ibaNet interface
ibaNet protocols
Cycle time
Number of signals
32Mbit Flex
Selectable beginning with
0.5 ms (1540 Bytes),
data amount depending
on cycle time
Up to 1024 analog values
(BYTE, INT, WORD, DINT,
DWORD, FLOAT, Big/Little
Endian) + up to 1024 digital
signals (bits)
A total max. of 4060 Bytes at a cy-
cle time of 1.4 ms
32Mbit (Compatibility mode
)
1 ms
Up to 512 analog values
(BYTE, INT, WORD, DINT,
DWORD, FLOAT, Big/Little
Endian; max. 1984 Bytes)
+ up to 512 digital signals (bits)
3Mbit (Compatibility mode
*
)
1 ms
Up to 64 analog values
(INT or FLOAT)
+ up to 64 digital signals (bits)
Connector type
2 ST plug connector (62.5 µm/125 µm) for RX and TX, max.
2000 m cable length without repeater
More interfaces, operating and indicating elements
Voltage supply
24 V DC ±10% not stabilized
Current consumption
Max. 500 mA
Connection
2-pin Phoenix connector, can be screwed
Voltage switch
HW version A9 and lower: On/off switch for the whole device
HW version B0 and higher: No on/off switch included
Rotary switch
Operation modes, address switch (in the cascade)
Ethernet
10/100 Mbit/s, RJ45 connector
Other interfaces
USB (only for service purposes)
Grounding screw
Indicators
4 LEDs for device status
4 LEDs for PROFIBUS status bus 0
4 LEDs for PROFIBUS status bus 1
2 LEDs for Ethernet interface
*
With ibaPDA version V6.20.2 or higher