Manual
ibaBM-DP
130
Issue 1.7
13.2.3 Mode 1 – PDA 32 Reals
This mode is used to read up to 32 real values and 32 digital signals from the PROFIBUS
(OUT 136 Bytes).
13.2.3.1 Output data
OUTPUT DATA
Byte no.
Offset
Contents
Remark
1
0
Status
not used
2
1
Status
not used
3
2
Status
not used
4
3
Status
not used
5
4
7 6 5 4 3 2 1 0 Dig. outputs channel 0...7
6
5
15 14 13 12 11 10 9 8 Dig. outputs channel 8...15
7
6
23 22 21 20 19 18 17 16 Dig. outputs channel 16...23
8
7
31 30 29 28 27 26 25 24 Dig. outputs channel 24...31
9
8
MSB
Analog output channel 0
Real (4 byte), Big Endian Motorola
10
11
12
LSB
13
12
MSB
Analog output channel 1
Real (4 byte), Big Endian Motorola
14
15
16
LSB
16
Analog outputs in total:
32 Longs (Real), Big Endian Motorola
133
132
MSB
Analog output channel 31
Real (4 byte), Big Endian Motorola
134
135
136
LSB
13.2.3.2 Input data
No inputs
13.2.3.3 GSD File
GSD file name
Remark
iba_0F02.gsd
-
13.2.3.4 Applications
ibaPDA
ibaLogic
System coupling
SIMATIC TDC
NO SIMATIC S7 (FW < 2.0 for S7-300, FW < 3.0 for S7-400), SIMADYN D