Chapter 4 PLC Features
4.1 Device Memory
4-6
ME0416-1A
Relation between SM Signals and System Data Assignment (2/2)
Address
(Decimal)
Assignment Details
Remarks
SM64-71 Gateway Alarm
With SM71 on the top, the last two digits of gateway alarm code to be
assigned
SM72
SEMG:
System in Emergency Stop
Emergency stop by EMC terminal on gateway board
SM73
Reserved
SM74
ALML:
Gateway Board in Light
Malfunction
Turns on when gateway alarm in level available to continue operation
generated
SM75
ALMH:
Gateway Board in Critical
Malfunction
Turns on when gateway alarm in cold start level generated
SM76
RMDS:
MODE Switch in MANU
MANU: On
AUTO: Off
SM77
TER:
Driver Communication Error
Occurred
Turns on when gateway alarm 8DD or 8DE generated
8DD: Unit Connectivity Error
8DE: Driver Unit_Total Frame Irregular Communication Error
SM78
CER:
Fieldbus Error Occurred
Turns on when gateway alarm 850 generated
850: Fieldbus Communication Error
SM79
On When Power Supplied
A bit with no special meaning, established to make it same specifications
as MCON-LC
SM80
Axis 0 in Light Malfunction
Turns on when axis maintenance alarm generated
The maintenance alarm indicates the driver board alarm codes 048, 04E,
04F and 06B.
SM81
Axis 1 in Light Malfunction
SM82
Axis 2 in Light Malfunction
SM83
Axis 3 in Light Malfunction
SM84
Axis 4 in Light Malfunction
SM85
Axis 5 in Light Malfunction
SM86
Axis 6 in Light Malfunction
SM87
Axis 7 in Light Malfunction
SM88
Axis 0 in Link
Turns on when an axis exists
SM89
Axis 1 in Link
SM90
Axis 2 in Link
SM91
Axis 3 in Link
SM92
Axis 4 in Link
SM93
Axis 5 in Link
SM94
Axis 6 in Link
SM95
Axis 7 in Link
SM96
Axis 8 in Light Malfunction
Turns on when axis maintenance alarm generated
The maintenance alarm indicates the driver board alarm codes 048, 04E,
04F and 06B.
SM97
Axis 9 in Light Malfunction
SM98
Axis 10 in Light Malfunction
SM99
Axis 11 in Light Malfunction
SM100 Axis 12 in Light Malfunction
SM101 Axis 13 in Light Malfunction
SM102 Axis 14 in Light Malfunction
SM103 Axis 15 in Light Malfunction
SM104 Axis 8 in Link
Turns on when an axis exists
SM105 Axis 9 in Link
SM106 Axis 10 in Link
SM107 Axis 11 in Link
SM108 Axis 12 in Link
SM109 Axis 13 in Link
SM110 Axis 14 in Link
SM111 Axis 15 in Link
SM112-127 Reserved