Chapter 3 Installation,
iring, Conguration
3.2
Wiring
ME0416-1A
3-8
[Electric wire diameter used for RCON-PS2 200V power supply wiring]
For the wires to be connected to the power connector, use the following applicable wires.
Compatible wire
Signal name
Content
Compatible wire
L1
Phase 1
Motor drive power supply
AWG14 ~ 8 (Copper wire)
L2
Phase 2
L3
Phase 3
Protection
Grounding
* Use cables with their rated temperature on the isolation sheath at 60°C or higher.
The controller current consumption varies depending on the controller model and the motor type
of the actuator to be connected. Refer to RCON System instruction manual "Specification Section
Chapter 2, 2.3 Specifications/ Power supply capacity".
Caution
Use wires with diameter large enough for allowable current higher than the current
actually used.
Smaller diameter of the cables than applicable could cause abnormal high heat when
flowing current. This could melt the coating on cables and set a fire.